Clocking the Meter (Natural Gas)

 1.  Turn off all other appliances and pilots.

 2.  Turn on the boiler and set the boiler to high fire.

 3.  Ensure the boiler has a large load to heat, so that the boiler will not shut off.

 4.  With a Stop-Watch, record the number of seconds for the smallest dial to make 1 full revolution.

 5.  CFH = (3600 x Dial Size) / Seconds.

 6.  CFH x 1000 (check local Btu content) = Input Btu’s.

 

Note

For 2 PSI meters multiply CFH x 1.097

For Metric meters multiply CFH x 35.3

For 2 PSI metric meters multiply CFH x 1.097 x 35.3

For Altitude above 4,500’ deduct 2% per 1,000’ of altitude from the Input Btu’s.