Combustion Test Target Ranges

Figure:  Gas valve and fan

The Low Fire (zero-offset) valve adjustment cap on the gas valve has been factory set. Do not adjust this screw in the field 

unless indicated  in these instructions. 

After converting the appliance to propane, a combustion (CO

2

) reading must be taken by a qualified technician using 

properly functioning and calibrated combustion analyzing equipment and the results compared to the values in Table 1.

Propane 

CO

2

 Value (%) at High Fire with front 

cover open

CO

2

 Value (%) at Low Fire with front 

cover open

Max. CO

2

 value

11.5%

Value at High Fire 

Minus -

 0.3%

Min. CO

2

 value

9.8%

9.5%

Table 1 

 - CO

2

 values at High and Low Fire

2

|