11.2.1 Temperature issues
Temperature issues
Issue
Diagnosis
Fix
Low heat
Operating temperature
too low.
Increase temperature target.
Load configuration
improperly set up.
Review load configuration parameters.
Boiler undersized.
Refer to Load Calculation vs. Boiler
Output.
Air trapped within
system.
Bleed system as required.
Improper system
piping.
Refer to recommended piping guidelines
for the respective boiler model.
System pump
undersized.
Check pump manufacturer’s data.
Defective thermostat.
Refer to manufacturer’s instructions.
Boiler cycling on
operating/ safety
controls.
Check operation with
Ohmmeter/Voltmeter.
System radiation
undersized.
Check manufacturer’s rating tables for
capacity per foot.
Temperature exceeds
mercury thermostat setting
Incorrect anticipator
setting.
Check with Ammeter.
Thermostat not level.
Check level.
One or more zones do not
heat properly
Air trapped within zone
(s) piping
Vent system/zone as required.
Low radiation/
excessive heat loss.
Check actual length of pipe using
radiation / heat loss calculation.
Low flow rate to zone
(s).
Check temperature drop across zone.
Defective zone valve/
zone circulator.
Check operation per manufacturer’s
instructions.
58
Section: Troubleshooting
Summary of Contents for EBX Series
Page 10: ...Intentionally left empty 10 Section Specifications ...
Page 11: ...11 Connection specifications ...
Page 12: ...Intentionally left empty ...
Page 14: ...4 3 Internal view 14 Section Introduction ...
Page 16: ...Intentionally left empty ...
Page 18: ...Intentionally left empty ...
Page 48: ...Intentionally left empty ...
Page 50: ...Intentionally left empty ...
Page 60: ...Intentionally left empty ...
Page 61: ...61 Appendices Wiring diagrams Figure 29 EBX series Boilerinternal wiring diagram ...
Page 62: ...Intentionally left empty ...
Page 63: ...63 ...