Checking boiler / water heater settings
Check
Ensure the water temperature to the heating coil is sufficient to meet the heating
demands of the space.
□
3.2 Default settings
The following table shows the factory-default settings.
Default - Basic Settings
Heating Mode
1 stage
Cooling Mode
2 stage
Boiler Heating
1 stage and 2 stage
Temperature
°F
Pump Enable
On
Tankless Mode
Off
3.3 Default fan speed settings
For fan speed defaults and ranges, see the table below:
AHU - Fan speed Operation
W1
Heating stage 1 = 600 CFM
Range 300-800
W2
Heating stage 2 = 800 CFM
Range 300 – 1000 (must be ≥ than heating stage 1)
Y1
Cooling stage 1 = 700 CFM
Range 300 – 800
Y2
Cooling stage 2 = 1000 CFM
Range 300-1000 (must be ≥ than cooling stage 1)
G
Fan on speed = 400 CFM
Range 150-1000
Note
For safety reasons, a switch is built into the door. The switch prevents the fan from
operating if the door is not installed. With the door removed, the appliance's control board
will remain powered, enabling programming of the mobile app.