Heating capacity
AHU 800 - Heating Capacity (Entering Dry Bulb Temperature 70°F) @ 800 CFM
Entering Water Temperature
3 GPM
4 GPM
5 GPM
195°F (90°C)
68.6 MBH
73.2 MBH
76.2 MBH
190°F (88°C)
65.7 MBH
70.2 MBH
73 MBH
180°F (82°C)
60 MBH
64.1 MBH
66.8 MBH
170°F (77°C)
54.4 MBH
58.1 MBH
60.5 MBH
160°F (71°C)
48.7 MBH
52.1 MBH
54.3 MBH
150°F (66°C)
43.1 MBH
46.2 MBH
48.1 MBH
140°F (60°C)
37.6 MBH
40.2 MBH
41.9 MBH
130°F (54°C)
32 MBH
34.3 MBH
35.8 MBH
120°F (49°C)
26.5 MBH
28.5 MBH
29.7 MBH
110°F (43°C)
21.1 MBH
22.6 MBH
23.7 MBH
Table 1
Heating Capacity rating at 800 scfm (cubic feet / minute) - AHU 800
AHU 1200 - Heating Capacity (Entering Dry Bulb Temperature 70°F) @ 1200 CFM
Entering Water Temperature
3 GPM
4 GPM
5 GPM
195°F (90°C)
81.3 MBH
87.7 MBH
91.8 MBH
190°F (88°C)
78 MBH
84.1 MBH
88.1 MBH
180°F (82°C)
71.3 MBH
76.9 MBH
80.6 MBH
170°F (77°C)
64.6 MBH
69.8 MBH
73.1 MBH
160°F (71°C)
58 MBH
62.6 MBH
65.6 MBH
150°F (66°C)
51.4 MBH
55.5 MBH
58.2 MBH
140°F (60°C)
44.8 MBH
48.4 MBH
50.8 MBH
130°F (54°C)
38.3 MBH
41.4 MBH
43.4 MBH
120°F (49°C)
31.8 MBH
34.3 MBH
36 MBH
110°F (43°C)
25.3 MBH
27.4 MBH
28.7 MBH
Table 2
Heating Capacity rating at 1200 scfm (cubic feet / minute) - AHU 1200
8
Section: Specifications
Summary of Contents for AHU Series
Page 1: ...INSTALLATION OPERATING MANUAL Air Handling appliances AHU 800 AHU1200 AHU 1600...
Page 2: ......
Page 5: ...5 3 Fault Codes 67 Air handling appliance parts diagram 70 3...
Page 6: ...This page is intentionally left blank...
Page 18: ...This page is intentionally left blank...
Page 60: ...This page is intentionally left blank...