background image

11

INSTALLATION AND OPERATION INSTRUCTIONS

IBC INDIRECT WATER HEATERS - ALL MODELS

It is recommended that the thermostat be set for the lowest possible temperature 

that satisfies your needs. This will also provide you with the lowest energy 

consumption and cost.
Check the water temperature at a hot water faucet soon after the tank thermostat 

has satisfied, and the circulator and the boiler have turned off. Adjust as needed.
Lowering the thermostat setting will not have an immediate effect on the water 

temperature because the stored water will have to be used and the thermostat 

must go through the cycle of heating cold water and satisfying at the new, lower 

temperature. Additional temperature checks should follow the completion of a 

heating cycle. Further adjustments may be required after you have used the 

water heater.

6) - Maintenance

The water heater is intended to provide many years of reliable service. 

Components, such as sensors and relief valves, may be subject to failures that 

require service. Depending on the quality of the water supply, sediment and/or 

scale may coat the heating coil in the tank and reduce hot water recovery rate. 

Failure to use the correct procedures or parts can result in unsafe operation.
The owner should arrange to have the following inspections and simple 

maintenance procedures done at the suggested frequencies.

1.  Boiler and Domestic Water Piping (Annual)

Check all piping for signs of leakage at the joints, unions and shut-off valves. 

Repair as required.

2.  Temperature and Pressure Relief Valve (Annual)

3.  Sediment (Annual except where harsh water quality may require more 

frequent service)

Depending on water conditions, a varying amount of sediment may collect 

in the tank. Levels requiring service are indicated by a small temperature 

difference between the boiler supply and return lines, and a reduced recovery 

rate. Repeated flushing usually clears such material. As a preventive 

measure, water should be drawn from the drain valve until it runs clear and 

the installation of a water filter should be considered. 

4.  Scale (Annual)

Hard water may cause scale buildup on the outside of the heating coil 

inside the tank. A water softener will help prevent this problem. Symptoms 

are identical to sediment buildup. If repeated flushing does not resolve the 

problem, chemical cleaning may be required. Proceed as follows:

Chemical cleaning of the heating coil:

1.  To avoid water damage, shut off the cold water supply to the water heater.
2.  Make a note of the DHW temperature control setting on the IBC control, 

and turn off the power to the boiler and water heater.

3.  Relieve the water pressure in the tank by opening a hot water faucet. This 

will reduce the risk of scalding.

4.  Remove the relief valve from the water heater.
5.  Drain the water heater until the water is at a level equal to 3” above the 

thermostat well. This level will cover the coil and the thermostat.

CAUTION

As a precaution:
After the water heater 

has reached its setpoint 

temperature, the installer 

should locate a faucet that 

is unprotected by an over-

temperature device.
Turn the faucet on full, and 

allow it to run long enought to 

ensure the water and piping 

have been heated up to the 

discharge temperature of the 

tank.
Using an accurate 

thermometer, test the water 

temperature to ensure it is 

withing plus or minus 10°F of 

the setpoint. If there is more 

deviation, the cause should 

be determined and corrective 

measures taken.

Summary of Contents for 30

Page 1: ...IBC 115 HO C FOR SINGLE WATER HEATER INSTALLATIONS For service or repairs to the water heater call your heating contractor Your water heater has been manufactured to provide years of service In order...

Page 2: ...n hazardous conditions that could result in property damage and injury to occupants which in extreme cases might result in death When using electrical appliances basic safety precautions to reduce the...

Page 3: ...es for Hot Water Supply Systems ANSI Z21 22 latest edition This valve must be marked with a maximum set pressure not to exceed the marked working pressure of the water heater Install the valve into an...

Page 4: ...400 14 0 6 6 T P VALVE 1 1 4 NPT BOILER SUPPLY 1 1 4 NPT BOILER RETURN 1 1 2 NPT DOM COLD INLET SENSOR WELL DRAIN C UNITS 8 0 8 0 9 5 3 4 NPT RECIRC PORT 1 1 2 NPT HOT OUTLET T P VALVE BOILER SUPPLY...

Page 5: ...low through the water heater coil and the pressure drop at minimum flow Calculate the pressure drop across all piping and fittings connected to the water heater zone Be sure to include all zone valves...

Page 6: ...software that can provide DHW priority with simultaneous space heating allowed during moderate heating demands C Locating the water heater The water heater should be located in an area where water le...

Page 7: ...supply line to the heater strip back to the tank or nearest mains piping and cap off If oil heating system is to be abandoned completely ensure proper removal and disposal of old oil tank and remainin...

Page 8: ...g system that is either in place or is to be installed for a new hydronic system installation See Schematic drawings in Section 8 for direction 2 It is recommended that minimum size 1 pipe be used on...

Page 9: ...tallation Manual for the boiler as well Temperature Sensor The Temperature Sensor supplied with the IBC Water Heater is an NTC Thermistor type with a resistance of 10 000 ohms at 25 C and 3892 IBC doe...

Page 10: ...HW operation if the DHW Priority setting is higher than the other heating loads Temperature Adjustment The tank sensor controls the maximum water temperature in the water heater If it is set too high...

Page 11: ...e frequent service Depending on water conditions a varying amount of sediment may collect in the tank Levels requiring service are indicated by a small temperature difference between the boiler supply...

Page 12: ...to flush all of the cleaning solution from the tank 11 Reinstall the relief valve and the drain piping 12 Open the cold water supply and fill the tank with water Purge the air from the tank and the pi...

Page 13: ...n Follow steps for Boiler does not operate Check for 24VAC at the zone valve while there is a call for heat if correct voltage is available and connections are good replace the zone valve If the zone...

Page 14: ...with IBC Water Heater Interlock 1 Interlock 2 Therm 1 Therm 2 Therm 3 Outdoor S Indoor S 2nd Loop S DHW S Boiler Net Ext Cont White Green Black Fuse 5A Fuse 5A Fuse 5A Fuse 5A G1 DHW Pump P2 Fan Coil...

Page 15: ...20 115 Pumps Only IBC SL 20 115 BOILER IBC DHW Domestic Hot Water Sensor DHW Pump P1 Fan Coil Pump P2 Outdoor Sensor Fan Coil Thermostat Mechanical Drawing 3 FAN COIL NOTE IBC VFC Series boilers have...

Page 16: ...op S DHW S Boiler Net Ext Cont White Green Black Fuse 5A Fuse 5A Fuse 5A Fuse 5A G1 G2 G3 G4 G5 G6 G7 G8 O1 O2 O3 O4 O5 O6 O7 O8 O9 O10 O11 O12 O13 O14 O15 O16 O17 O18 O19 O20 O21 O22 Auxiliary Interl...

Page 17: ...iping w DHW Pump and Baseboard system Zone Valves Domestic Hot Water Sensor BB Zone 1 Thermostat Mechanical Drawing 5 BB Zone 1 Valve ZV1 BB Zone 2 Valve ZV2 BB Zone 3 Valve ZV3 Zone Valve end switch...

Page 18: ...Well Drain Valve and Temperature Pressure Relief Valve An IBC Temperature Sensor is shipped loose with the tank to be inserted into the Temperature Well and wired to the IBC Boiler Control Board on Te...

Page 19: ...115 F 140 F 115 F 140 F 115 F 140 F 115 F 50 000 139 164 67 92 170 195 67 92 60 000 152 183 80 111 183 214 80 111 80 000 179 219 107 147 210 250 107 147 100 000 205 256 133 184 236 287 133 184 120 000...

Page 20: ...115 F 140 F 115 F 140 F 115 F 140 F 115 F 50 000 139 164 67 92 170 195 67 92 60 000 152 183 80 111 183 214 80 111 80 000 179 219 107 147 210 250 107 147 100 000 205 256 133 184 236 287 133 184 120 000...

Page 21: ...21 INSTALLATION AND OPERATION INSTRUCTIONS IBC INDIRECT WATER HEATERS ALL MODELS DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE Service Record Notes...

Page 22: ...ATION AND OPERATION INSTRUCTIONS 22 IBC INDIRECT WATER HEATERS ALL MODELS IBC Technologies Inc 1445 Charles Street Vancouver BC Canada V5L 2S7 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 1...

Reviews: