background image

SAST1029

Page 

2

 

 

1. 

Water to be tested should be taken from a tap after the water softener

 

2. 

Measure 10ml of water into plastic bottle supplied (approximately 1/3 full)

 

3. 

Add  one  Yes/No  tablet  to  sample  water,  replace  cap  and  shake  until  tablet
has completely dissolved.

 

 (NOTE: do not handle Yes/No tablet with fingers)

 

4. 

The  final  colour  to  be  obtained  for  soft  water  is  green.  (Note:  The  shade  of
green may vary.) If the colour turns red, the water is above 20 mg/l hardness,
therefore another regeneration is recommended.

 

5. 

Rinse plastic bottle after each test has been completed.

 

6. 

When  used  as  above,  the  tablets  change  the  colour  from  green  to  red  at  a
hardness of approximately 20ppm based on a sample volume of 10mls.

          

Other hardness test kits are available for more accurate testing eg.

Hardness Tablets

Directions:

Take  a  50ml  sample  of  water  in  a  screw  capped  bottle.  Add  one  (1)
tablet to sample, shake or crush to disintegrate. Repeat until last trace
of  reddish  tinge  disappears.  The  final  colour  is  usually  blue  but  with
some water a greyish coloured end point is obtained.

Using 50ml sample -
Hardness ppm = (number of tablets x 40) - 20

LR (BW) Tablets

Directions:

Take  a  100ml  sample  of  water  in  a  screw  capped  bottle.  Add  one  (1)
tablet to sample, shake or crush to disintegrate. Repeat until last trace
of  reddish  tinge  disappears.  The  final  colour  is  usually  blue  but  with
some water a greyish coloured end point is obtained.

Using 100ml sample -
Hardness ppm = (number tablets x 2) – 1

Contact IBC Water if further details are required.

HARDNESS TEST

Summary of Contents for SAST1029

Page 1: ...OPERATING INSTRUCTIONS Model SAST1029 Serial No Telephone 07 3219 2233 Facsimile 07 3219 2266 Email sales ibcwater com au Website www ibcwater com au FILTRATION WATER TREATMENT PRODUCTS for commercial...

Page 2: ...imately 20ppm based on a sample volume of 10mls Other hardness test kits are available for more accurate testing eg Hardness Tablets Directions Take a 50ml sample of water in a screw capped bottle Add...

Page 3: ...s call C 3 Daily Water Usage in litres call D For household situations allow 250 litres per person per day CALCULATION N 1000 x C D x H Select nearest lower whole number If necessary consult your deal...

Page 4: ...e unit must be installed in accordance with local codes 7 Do not over tighten connections 8 Drain line ID must be at least 12mm 9 Teflon tape should be used when installing he drain fitting into the c...

Page 5: ...S 1 Floor Level a Use any length of 1 2 pipe or larger 2 Control Level a For 30 or less of drain line use 1 2 pipe or larger b For 30 or more of drain line use 3 4 pipe or larger Never connect the dra...

Page 6: ...ensure the bypass valve is closed Run the nearest cold water tap for a least 15 minutes to ensure the resin bed is flushed BRINE TANK 1 Place at least 25kg of a coarse refined grade of salt Water Sof...

Page 7: ...SAST1029 Page 7 During regeneration raw hard water is bypassed to service so it is advisable to regenerate the unit when water is not needed...

Page 8: ...SAST1029 Page 8 Water Conditioning Control System Installation Operating and Maintenance Manual 541 030 VALVE...

Page 9: ...tube and up through the resin bed to drain This slow flow of water pushes the brine solution through the resin bed In brine draw concentrated salt brine is drawn from the brine tank and directed to f...

Page 10: ...w o rings 1 16 529 244 Gasket Cross Over Port 1 17 541 244 Body Stem Assembly 1 18 185 024 1 O ring Small Seat Insert 1 19 541 204 Seal Insert 1 20 185 028 12 O ring Large Seat Insert 1 21 541 256 Ma...

Page 11: ...SAST1029 Page 11...

Page 12: ...set b Verify water usage matches system size and salt dosage c Replace safety float 4 Loss of resin a Faulty air check in storage tank b Leak at the distributor tube a Clean or replace air check b Ve...

Page 13: ...d that the outside edges of the main diaphragm are tucked into the valve body Rinse Adjustment Valve Replacement 1 Place the bypass valve into bypass position 2 Relieve the system pressure Remove the...

Page 14: ...ce a hand under the backcap and remove the backcap The check disc return spring will fall into your hand 5 Remove the check disc from the back of the body stem assembly 6 Inspect the rubber seal on th...

Page 15: ...or Cabinet Model Float Distance X SAS0715 100mm SAS0922 200mm SAS1029 260mm Adjustment of Softener Brine Valve 1 Lift float rod to full up position 2 Set float to distance shown Measure from the top o...

Reviews: