IBC control MiniMax Manual Download Page 10

OPERATIONAL INDICATIONS

On

"Power on" is lit continuously. 
It flashes when the control unit has tripped.

Run

Comes on when the motor is to rotate, i.e. when the input signal exceeds 
the threshold value.

Rotation

Flashes when the magnet passes the magnetic sensor, regardless of the 
rotation monitor DIP switch setting. 
Flashes even if the input signal is lower than the threshold value.

Rotation monitor

Probable fault cause 
during installation

Probable fault cause
during operation

Alarms and trips unless a pulse is received every 5 minutes.     

  

Magnet facing the wrong way

- Magnetic sensor incorrectly connected; see “Connections” on  
 

             

pages 11 -12.

- Too wide a gap between the magnetic sensor and magnet; max 15 mm

-

 Broken belt

- Belt slipping 
- Stuck wheel
- Magnetic sensor or magnet not intact

Overtemp. motor

Probable fault cause

 

Alarms and trips if motor winding temperature is too high.
The thermal contact in the motor reverts to normal mode when the 
temperature drops.

See "Overcurrent" on page 9.

Overvoltage

Alarms and trips if the input voltage exceeds 276 V for more than 
4-5 seconds

.

Undervoltage

Alarms and trips if the input voltage falls below 195 V for more than  
4-5 seconds.

ALARMS

   

All alarms remain in state.

     

Continued on next page

8

Summary of Contents for MiniMax

Page 1: ...IBCcontrol Made in Sweden MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MiniMax Article no F21037501 Set of EMC glands as an option...

Page 2: ......

Page 3: ...nical data 6 Functions 6 DIP switch 7 Operational indications 8 Alarms 8 9 Settings via potentiometer 10 Push button 10 Connection diagram 11 Connections 11 12 Checks before powering up the control un...

Page 4: ...emented Disposal and recycling When replacing components or when the control unit in its entirety need replacing please follow the advice below The aim should always be maximum possible recycling of r...

Page 5: ...in power before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electric shock resulting in serious injury or death Residual voltage remains...

Page 6: ...on of conformity with the requirements of the EMC Directive 2004 108 EC The control unit is approved according to the requirements of the EMC Directive 2004 108 EC and is tested according to standard...

Page 7: ...ning begins and the rotor turns for 10 seconds at minimum rpm The rotation monitor a magnet fitted to the rotor with an associated magnetic sensor stops the converter and generates an alarm in the cas...

Page 8: ...0 W Input current max 2 8 A Incoming fuse max 10 A Output voltage 3x0 230 V Min frequency 1 20 Hz Max frequency 40 100 Hz Motor output max 370 W Motor current max 1 9 A Exact value cannot be obtained...

Page 9: ...0 0 1 0 4 20 mA 0 0 1 0 1 0 Cleaning 1 Cleaning function set to ON position When the wheel has stopped for 30 minutes the cleaning function is activated and the wheel rotates at minimum speed for 10...

Page 10: ...received every 5 minutes Magnet facing the wrong way Magnetic sensor incorrectly connected see Connections on pages 11 12 Too wide a gap between the magnetic sensor and magnet max 15 mm Broken belt Be...

Page 11: ...asure motor resistance it should be identical on all phases Short circuit between phases in the cable Earth fault in motor or cable Overcurrent MiniMax limits current at 4 A and trips then after 4 5 s...

Page 12: ...tor temperature will increase Acc Acceleration time 0 30 s Factory set to max does not need adjustment Ret Retardation time 0 30 s Factory set to max does not need adjustment Threshold value The contr...

Page 13: ...ax 2 A 250 V AC 3 x 230 V Max 370 W 13 14 15 T T Larmrel Termo kontakt 1 M 2 3 4 5 3 Rotation monitor A1 A2 A3 1 2 6 10 12 w S br Manual high low speed Input signal Run 3 5 9 11 Reset 1 2 3 Pot 10 k P...

Page 14: ...t be jumped if external start not used Rotation monitor 9 10 White cable connected to terminal 9 brown to terminal 10 The magnet is installed with south side S towards the transmitter Max gap 15 mm Re...

Page 15: ...ltage Make sure the cleaning DIP switch is set to ON and the input signal is disconnected When power is switched on the wheel will rotate at minimum rpm for 10 seconds Checking the rotation monitor Th...

Page 16: ...GLAND Motor cable Incoming EKK 3G1 5 Not shielded lflex Classic 110 CY 7G0 5 Shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Dir...

Page 17: ...PERSONAL NOTES 15...

Page 18: ...16 PERSONAL NOTES...

Page 19: ...17 PERSONAL NOTES...

Page 20: ...IBC control AB Br nnerigatan 5 A 263 37 H gan s Sverige Tel 46 0 42 33 00 10 Fax 46 0 42 33 03 75 www ibccontrol se info ibccontrol se IBCcontrol F21037905GB Version 1 0 2016 03 01...

Reviews: