Page 1
Contents
The Default Display Screen.......................................................................... 2
The Clock Display Screen ............................................................................ 2
1.0 Quick Start Options ................................................................................ 3
2.0 Standard Menu Options ......................................................................... 3
2.1 To Change the Mode .................................................................................................................... 3
2.2 To Set the Fan Speed (Multi fan speed models only)................................................................... 4
2.3 To Change the HeatFan Setting .................................................................................................. 4
2.4 To Set the Run Timer (After Hours Timer) .................................................................................... 4
2.5 To Edit the Setback Temperatures................................................................................................ 4
3.0 To Edit the System Settings (Service Personnel Only). ...................... 5
3.1 To Change the Compressor Delays.............................................................................................. 5
3.2 To Set the Deadband.................................................................................................................... 5
3.3 To Set the Control Band ............................................................................................................... 6
3.4 To Edit the Service Timer.............................................................................................................. 6
3.5 To Select the Forced Vent Input Message.................................................................................... 7
3.6 To Select the Remote On/Off Input Message ............................................................................... 7
3.7 To Select the System Fault Message ........................................................................................... 7
3.8 To Select the Service Timer Message .......................................................................................... 7
3.9 To Edit the Custom Message........................................................................................................ 7
4.0 Clock Menu Options ............................................................................... 8
4.1 To Set the Clock ........................................................................................................................... 8
4.2 To Edit the Timeclock Programs ................................................................................................... 8
4.3 To Set Holidays............................................................................................................................. 9
4.3 To Set Daylight Savings................................................................................................................ 9
5.0 Installation and Commissioning.......................................................... 10
5.1 Touchpad Dipswitch Confi gurations ........................................................................................... 10
5.2 C-LCD-122-TL Connection Diagram .......................................................................................... 11
The Default Display Screen
Setpoint Tem per a ture
Relay Confi guration
Upper case indicates the
relay is energised.
F
= Fan
C
= Compressor
R
= Rev. Valve
R
R
H
= Elect. Heat
P
= Pump
Conditioning Mode
A
= Auto
V
= Vent only
C
= Cool
H
= Heat
Operating Mode
TC
= Timeclock
RT
= Run Timer function
SB
= Setback function
22
.
5
O
c TC
O
O
FC c RR A
The Clock Display Screen
Optional Clock Mode Required
Time
Date
Year
Day
0 1 :3 1
p
M o
0 2 D e c,0 2
Page 10
0
S
0
V
V
1
V
2
Auxiliary Socket
DIP Switches
D1 D2 V- V+
Terminal
Touchpad
Proof of Flow Input.
(See JP1 notes)
Heating
Control Active
Fan
Control Active
Cooling
Control Active
Heating
Control Active
240 VAC
Line in
Flow Proved LED
Relay 5 LED
Relay 1 LED
Relay 2 LED
Relay 3 LED
Relay 4 LED
JP1
RSP
relay 1
C1
A N E
NO
5
NC
5 C5 F- F+ D1 D2 V- V+ SH S1
NC1 NO1 C2 NC2 NO2
O
O C3 NC3 NO3 C4 NC4 NO4
O
O
relay 2
relay 3
relay 4
relay 5 flow
touchpad
sensor
0-10V
240 V
Heat 2
Heat 1
Cool 2
Cool 1
Fan
Se
ns
or
Analogue
Output 2
Heating
Analogue
Output 1
Cooling
Analogue
Output
Common
BBP-5 Relay Module DIP Switch Settings
Number
Function
OFF
(Factory Default)
ON
1
Compressor
Delay
Software Selectable
(4 minute default)
4 seconds
(max)
2
IAS Factory
Use Only
3
IAS Factory
Use Only
4
Heat Type
Reverse Cycle
EDH or
Cool Only
NOTES:
JP1 - remove shorting jumper from JP1, located behind
Flow Input terminals, for external proof of fl ow
input. Short JP1 for constant fl ow (no proving)
LED - The green relay LEDs when lit indicate that
the NO output for each relay is energised.The
fl ow LED indicates fl ow proved when lit.
5.2 C-LCD-122-TL Connection Diagram