8
CALIBRATION
User adjustable / factory calibration:
Use the ENTER button to advance through the 11 point output calibration as well as the other
analogue related calibration, as follows:
Counts: 0.00000
XXXXXXX
Counts for 0.00000Vdc output
Counts: 1.00000
XXXXXXX
Counts for 1.00000Vdc output
Counts: 2.00000
XXXXXXX
Counts for 2.00000Vdc output
Counts: 3.00000
XXXXXXX
Counts for 3.00000Vdc output
Counts: 4.00000
XXXXXXX
Counts for 4.00000Vdc output
Counts: 5.00000
XXXXXXX
Counts for 5.00000Vdc output
Counts: 6.00000
XXXXXXX
Counts for 6.00000Vdc output
Counts: 7.00000
XXXXXXX
Counts for 7.00000Vdc output
Counts: 8.00000
XXXXXXX
Counts for 8.00000Vdc output
Counts: 9.00000
XXXXXXX
Counts for 9.00000Vdc output
Counts: 10.00000
XXXXXXX
Counts for 10.00000Vdc output
Out.Vdc XX.X
XXXX
Output monitor counts
Calibration of the output DC voltage monitor.
Batt/DC.Vdc XX.X
XXXX
Battery / Ext. power supply Vdc Span counts
Calibration of the Battery & external DC supply
for the main screen.
Charge mA XXX
XXXX
Charge current Span counts
Calibration of the battery charging current monitor.
Use the menu options as detailed at the bottom of the screen to navigate the various entries, and the other
buttons to make changes.
UP/DOWN
-
1 count modify
RIGHT/LEFT
-
100 count modify for DAC, 10 count for all else
HOLD
RIGHT/LEFT -
1000 count modify for DAC, 100 count for all else
See the Calibration record as supplied with your PDVS2mini for the original factory settings.
Any changes to settings are saved to EEprom.
Note: If you decide to make any adjustments to the above settings/calibration then please record the
original settings before you start.