5. EtherNet/IP (RCON-GW/GWG-EP)
7. PROFINET IO (RCON-GW/GWG-PRT)
Refer to the instruction manuals for each field network master unit and mounted PLC for the details.
Connector Name
EtherNet/IP, PROFINET IO Connector
Remarks
Cable Side
Ethernet ANSI/TIA/EIA-568-B Category 5
and above 8P8C modular plug equipped
with shield (RJ45)
Please prepare
separately
Controller Side
Ethernet ANSI/TIA/EIA-568-B Category 5
and above 8P8C modular Jack equipped
with shield (RJ45)
Pin
No.
Signal Name
Description
Applicable cable
diameter
1 TD+
Data
It is recommended
to prepare a
straight STP cable
in Category 5 or
above for the
Ethernet cable.
2 TD-
Data sending-
3 RD+
Data re
4 -
Disconnected
5 -
Disconnected
6 RD-
Data receiving-
7 -
Disconnected
8 -
Disconnected
6. PROFIBUS-DP (RCON-GW/GWG-PR)
Refer to the instruction manuals for each field network master unit and mounted PLC for the details.
Connector Name
PROFIBUS-DP Connector
Remarks
Cable Side
9-pin D-sub Connector (Male)
Please prepare separately
Controller Side
9-pin D-sub Connector (Female)
Pin
No.
Signal Name
Description
Applicable cable diameter
1 NC
Disconnected
Dedicated cable for
PROFIBUS-DP
(Type A: EN5017)
2 NC
Disconnected
3 B-Line
Communication Line B (RS485)
4 RTS
Request for Sending
5 GND
Signal GND (Insulation)
6 +5V
+5V Output (Insulation)
7 NC
Disconnected
8 A-Line
Communication Line A (RS485)
9 NC
Disconnected
Operation Mode Selected
In this controller, it is available to select six types of operation modes individually for each axis as the field
network type.
The settings are to be established with Gateway Parameter Setting Tool.
Operation Mode
Contents
Direct Indication
Mode
The target position, speed, acceleration/deceleration and pressing current limit can be
indicated with inputting a number. Monitoring of not only the current position, but also
the current speed and indicated current are available.
Simple Direct Mode
The target position can be indicated directly by inputting a value. Also, monitoring of the
current position is available in 0.01mm unit.
Those other than the target position are to be indicated in the position table, and the
setting can be done for 128 points at maximum.
Positioner 1 Mode
The 128 points of position data can be registered at the maximum and is able to stop at
the registered positions. Also, monitoring of the current position is available in 0.01mm
unit.
Positioner 2 Mode
This is the operation mode of the position data of 128 points at maximum set in the
position table. The monitoring of the current position is not available.
This mode is that the transferred data is reduced from Positioner 1 Mode.
Positioner 3 Mode
This is the operation mode of the position data of 128 points at maximum set in the
position table. The monitoring of the current position is not available.
This is the mode to control with the minimized number of signals to perform the
positioning operation by reducing the amount of sent and received data from Positioner
2 Mode.
Positioner 5 Mode
This is the operation mode of the position data of 16 points at maximum set in the
position table.
It is a mode that enabled to monitor the current position in 0.1mm unit by reducing the
number of position table from Positioner 2 Mode.
Starting Procedures
When using this product for the first time, make sure to avoid mistakes and incorrect wiring by referring to
the procedure below.
In this section, explains how to start up especially for RCON controller. Follow an instruction manual (DVD)
for each device for how to link to other devices, controllers and actuators that are linked in the network.
Troubleshooting (LED Display)
On RCON Gateway Unit, there are the monitor LEDs for the field network and communication.
You can confirm the communication establishment and also communication errors on these LEDs.
Refer to “Names for Each Part” for the position and name of each LED lamp.
Panel
Display
Color
Status
Explanation
T RUN
GN
Illuminating
Inside bus communication in normal conditions
Flashing
Waiting for initializing communication
OR
Illuminating
Inside bus communication in error
SYS
GN
Illuminating
Operating in normal conditions
OR
Illuminating
Gateway alarm being generated
STOP
RD
Illuminating
Confirmed STOP Signal input
(driver unit drive source being cut off)
OFF
No STOP Signal input confirmed
MODE
GN
Illuminating
In AUTO (automatic operation) Mode
OFF
In MANU (manual operation) Mode
C ERR
OR
Illuminating
Error occurred in field network
OFF
Field network operating in normal conditions
STATUS 0
-
-
Differs depending on field network (Refer to Field Network
Communication Conditions from 1 to 7)
STATUS 1
-
-
Differs depending on field network (Refer to Field Network
Communication Conditions from 1 to 7)
[Field Network Communication Conditions]
1. CC-Link (RCON-GW/GWG-CC)
Name
Panel
Display
Color
Status
Explanation
STATUS 0
RUN
GN
Illuminating
Succeeded in refresh and polling reception after
getting into network, or succeeded in refresh
reception
OFF
1. Not in network
2. Carrier detected for channel
3. Timeover
4. In hardware reset
STATUS 1
ERR
GN
Illuminating
1. CRC Error
2. Station number setting error at reset release
(65 stations or more including 0 or occupied
station number)
3. Baud rate setting error at reset release
(5 or more for baud rate setting)
Flashing
(Flash for
0.4sec)
Numbers changed from station numbers and
baud rate setting numbers at reset release
OFF
1. Communication in normal conditions
2. In hardware reset
2. CC-Link IE Field (RCON-GW/GWG-CIE)
Name
Panel
Display
Color
Status
Explanation
STATUS 0
MS
GN
Illuminating
Operation in normal conditions
OFF
Hardware error occurred
OR
Illuminating
Error being occurred
OFF
Operation in normal conditions
STATUS 1
NS
GN
Illuminating
Cyclic transmission in process
Flashing
Cyclic transmission paused
OFF
Cyclic transmission not conducted, parallel off
OR
Illuminating
Received data in error
OFF
Received data in normal conditions
LINK
-
GN
Illuminating
Linkup in process
OFF
Link-down in process
L.ER
-
OR
Illuminating
Received data in error
OFF
Received data in normal conditions
Top View of
Connector on
Controller side
1
8
No →
Check on Safety Circuit
Confirm that the stop circuit (drive source cutoff circuit) works in normal conditions.
↓Yes
No →
Check of Packed Items
Are all the delivered items present?
Contact your local IAI distributor
Installation and Wiring
* Refer to [Installation and Noise Elimination] in this first step guide
Install the controller and actuator and perform wiring according.
Important Check Item
•
Is frame ground (FG) connected?
•
Has the noise countermeasure been taken?
↓
← Yes
Initial Settings (Setup of Driver Units and Extension Units) * RC PC software is required
Establish the parameter settings for each controller.
PLC (Master Unit) Baud Rate
* Refer to PLC Instruction Manual.
Have the settings established for the PLC node addresses (station
numbers) and the baud rate.
Initial Settings (Setup of Gateway) * Gateway parameter setting tool is required
Have the settings done for the axis number setting, mode settings, field network communication speed, node addresses
(station numbers) and so on to suit to the system.
↓
No →
Power Supply
1) Supply the power to PLC (master unit).
2) In case of using the extension units, turn the power on for SCON connected to the extension units.
3) Supply the power to RCON.
Check the status of LED lamps to see the
cause of the error to have an appropriate
counteraction. Do the whole process from
the start if the cause of the error is not
clear.
↓
Communication Establishment Check
•
In case of using the extension units, turn the power on for SCON
connected to the extension units.
* Refer to “Troubleshooting” in this first step guide
•
Confirm that communication is established also on PLC (master unit).
* Refer to PLC Instruction Manual.
Check the circuit.
↓Yes
Now, it is succeeded to establish communication and ready for operation.
Move on to the system operation check and adjustment.
↓
Assembling RCON (Linking up Units) * Refer to RCON 24V/200V Driver Unit First Step Guide (ME0383/ME0397)
Join the units to use such as the gateway unit, driver unit, extension unit and so on.
↓
↓
Important Check Item
•
Is the control sequence applicable for
the continuous mode and the system?
↓Yes
5 1
9 6
Cable
Shield
Red B line (Positive side)
Green A line (Negative side)
Slave Devices
RCON PROFIBUS-DP Type
Master Unit
Grounding resistance at 100
Ω
or less
(Class D grounding)
5
9
6
1
Top View of
Connector on
Controller side
Master Unit
Switching Hub
Slave Devices
RCON-
EtherNet Type
or
RCON-
PROFINET IO Type
Ethernet Straight Cable,
Category 5 or more
Double shielded cable braided with
aluminum foil recommended