Copper wire: Connect a ground 
wire with a diameter of 1.6 mm 
(2mm

2

: AWG 14) or larger. 

Earth Terminal 
Grounding resistance at 100Ω or less 
(Class D grounding) 

Connect the ground line to the 
FG terminal block on the 
controller unit. 
Put a tool such as a screwdriver 
into the square slot and connect 
the line. 

1. Gateway Unit 

Item 

Specification 

External Dimensions 

30W × 115H × 95D [mm] 

Mass 

Approx. 157g 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

2. Terminal Unit 

Item 

Specification 

External Dimensions 

12.6W × 115H × 95D [mm]

 

Mass 

Approx. 49g 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

3. Linking Units 

Item 

Specification 

External Dimensions 

(42.6 + 22.6 × N) W × 115H × 95D [mm]    N: Total number of driver units and extension units 

Mass 

Approx. (206 + 180 × N1 + 99 × N2) g    N1: Number of driver units, N2: Number of extensions units 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Installation and Noise Elimination 

1.  Noise Elimination Grounding (Frame Ground) 

 
 
 
 
 
 
 
 
 
 

 

2.  Precautions regarding wiring method 

1)  Wire is to be twisted for the 24V DC power supply. 
2)  Separate the signal and encoder lines from the power   

supply and power lines. 

 

3.  Noise Sources and Elimination 

Carry out noise elimination measures for electrical devices   
on the same power path and in the same equipment. 
The following are examples of measures to eliminate noise   
sources. 
1)  AC solenoid valves, magnet switches and relays 

[Measure]  Install a Surge absorber parallel with the coil. 

2)  DC solenoid valves, magnet switches and relays 

[Measure]  Consider whether to attach a diode in parallel   

to the coil or to use a diode built-in type. 

 
4.  Cooling Factors and Installation 

Follow the specifications and dimensions shown below when you design and build a control board. 

Item 

Specification 

Item 

Specification 

Installation 
Orientation 

Vertical Orientation   
(Air outlet upwards)

Surrounding Air 
Temperature 

0 to 55

°

C (Refer to section of 

“Current Amperage” in ME0383) 
Derating equipped when with no 
fan unit

Installation 
Method 

Attached on DIN Rails 

Installation 
Condition 

See figure below 

Grounding 

Class D grounding 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

* Simple absolute units can be installed in close contact with each other. 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Installation Environment 

This product is capable for use in the environment of pollution degree 2 

*1

 or equivalent. 

*1  Pollution Degree 2: Environment that may cause non-conductive pollution or transient conductive 

pollution by frost (IEC60664-1) 

1.  Installation Environment 

Do not use this product in the following environment. 

  Location where the ambient temperature is out of the range between 0 and 55

°

C (with fan) or   

0 and 40

°

C (with no fan) 

  Location where condensation occurs due to abrupt temperature changes 

  Location where relative humidity exceeds 85%RH 

  Location exposed to corrosive gases or combustible gases 

  Location exposed to significant amount of dust, salt or iron powder 

  Location subject to direct vibration or impact 

  Location exposed to direct sunlight 

  Location where the product may come in contact with water, oil or chemical droplets 

  Environment that blocks the air vent [Refer to Installation and Noise Elimination] 

When using the product in any of the locations specified below, provide a sufficient shield. 

  Location subject to electrostatic noise 

  Location where high electrical or magnetic field is present 

  Location with the mains or power lines passing nearby 

2.  Storage and Preservation Environment 

The storage and preservation environment should comply with the same standards as those for the 
installation environment. 
In particular, when the machine is to be stored for a long time, pay close attention to environmental 
conditions so that no condensation forms. Unless specially specified, moisture absorbency protection is not 
included in the package when the machine is delivered. In the case that the machine is to be stored and 
preserved in an environment where condensation is anticipated, take the condensation preventive measures 
from outside of the entire package, or directly after opening the package. 
 

 

Connection to Peripheral Devices (Overall Wiring Diagram)

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

External Dimensions 

Model Plate 

(Large) 

Adhered 

Position 

N: Total number of driver units and extension units 

Do not share the ground wire with or connect 
to other equipment. Ground each controller.

Controller

Other 

equipment

Controller

Other 

equipment

Other 

equipment

Surge absorber

Relay 
coil

Relay coil

R

C

+24V

0V

+24V

0V

+

-

100mm or more

10mm

or more

100

mm or more

50

m

m

 o

r m

ore

Ceiling

RCON

Ceiling

10mm

10mm

Simple

Absolute

Unit

or more

or more

Ethernet

connector

Field Network
(Cables to be prepared by
user)

Ethernet (Cables to be prepared by user)

USB Cable
(Cables to be
prepared by
user)

(Cables
to be
prepared
by user)

Communication Cable

Motor/encoder Cable

Model Code: CB-ADPC-MPA□□□(-RB)

SCON Cable
Model Code: CB-FC-CTL□□□

(Cables to be prepared by user)

Connector Conversion Unit
Model Code: RCM-CV-APCS

Simple Absolute Unit

+24V, 0V

SCON-CB-*-RC

PSA-24

PC

TB-02

TB-03

PLC

Actuator

Summary of Contents for RCON-GW

Page 1: ...cations of Power Supply Item Specification Power Input Voltage Range 24V DC 10 Supply Current Refer to Current Amperage in RCON Driver Unit First Step Guide ME0383 Current Amperage Refer to Current Amperage in RCON Driver Unit First Step Guide ME0383 In Rush Current Refer to Current Amperage in RCON Driver Unit First Step Guide ME0383 Instantaneous Power Outage Endurance By 24V power supply Protec...

Page 2: ...the following environment Location where the ambient temperature is out of the range between 0 and 55 C with fan or 0 and 40 C with no fan Location where condensation occurs due to abrupt temperature changes Location where relative humidity exceeds 85 RH Location exposed to corrosive gases or combustible gases Location exposed to significant amount of dust salt or iron powder Location subject to d...

Page 3: ...thernet cable 2 TP0 Data 0 3 TP1 Data 1 4 TP2 Data 2 5 TP2 Data 2 6 TP1 Data 1 7 TP3 Data 3 8 TP3 Data 3 3 DeviceNet RCON GW GWG DV Refer to the instruction manuals for each field network master unit and mounted PLC for the details Connector Name DeviceNet Connector Remarks Cable Side MSTB2 5 5 STF 5 08 AU M Manufactured by PHOENIX CONTACT Enclosed in standard package Controller Side MSTB2 5 5 GF ...

Page 4: ...ting Confirmed STOP Signal input driver unit drive source being cut off OFF No STOP Signal input confirmed MODE GN Illuminating In AUTO automatic operation Mode OFF In MANU manual operation Mode C ERR OR Illuminating Error occurred in field network OFF Field network operating in normal conditions STATUS 0 Differs depending on field network Refer to Field Network Communication Conditions from 1 to ...

Page 5: ...l Display Color Status Explanation STATUS 0 MS GN Illuminating Initialization completed Flashing Initialization completed there is a diagnosis event RD Illuminating Exception error GN RD OFF Not initialized STATUS 1 NS GN Illuminating Online data exchange Flashing Online cleared RD Illuminating Parameter error Flashing Configuration error GN RD OFF Offline 7 PROFINET IO RCON GW GWG PRT Name Panel ...

Reviews: