Signal Assignments in Each Mode 

The signal assignment of I/O flat cable by the PIO pattern is as shown below. Follow the following table to connect the external 

equipment (such as PLC). 

Pin 

No. 

Category PIO 

Functions 

Selection in Parameter No. 25 (PIO Pattern) 

0 1  2  3  4  5 

6

(Note1)

 

7

(Note1)

 

Positioning 

mode 

Teaching 

mode 

256-point 

mode 

512-point 

mode 

Electro- 

magnetic 

valve mode 

Electro- 

magnetic 

valve mode 

Force 

Sensor Used 

Pressing 

Mode 1 

Force Sensor 

Used 

Pressing 

Mode 2 

Input 

Number of 

Positioning Points 

64 points 

64 points 

256 points 

512 points 

7 points 

3 points 

32 points 

5 points 

Home Return 

Signal 

 

 

 

 

 

 

 

 

Jog Signal 

 

 

 

 

 

 

 

 

Teaching Signal 

(Current Position 

Writing) 

 

 

 

 

 

 

 

 

Brake Release 

 

 

 

 

 

 

 

 

Output 

Signal during 

Operation 

 

 

 

 

 

 

 

 

Zone Signal 

 

 

(Note2)

 

 

(Note2)

 

 

 

 

 

 

Position Zone 

Signal 

 

 

 

 

 

 

 

 

1A 24V 

 

P24 

2A 24V 

 

P24 

3A 

– 

 

– 

4A 

– 

 

– 

5A 

Input 

IN0 PC1 

PC1 

PC1 

PC1 

ST0 

ST0 

PC1 

ST0 

6A IN1 

PC2 

PC2 

PC2 

PC2 

ST1 

ST1 

(JOG

PC2 ST1 

7A IN2 

PC4 

PC4 

PC4 

PC4 

ST2 

ST2 

(Note2)

 

PC4 ST2 

8A IN3 

PC8 

PC8 

PC8 

PC8 

ST3 

– PC8 ST3 

9A IN4 

PC16 

PC16 

PC16 

PC16 

ST4 

– PC16 ST4 

10A IN5 

PC32 

PC32 

PC32 

PC32 

ST5 

– 

– 

– 

11A IN6 

– 

MODE 

PC64 

PC64 

ST6 

– 

– 

– 

12A IN7 

– JISL 

PC128 

P128 – 

– 

– 

– 

13A IN8 

– 

JOG

 

– PC256 – 

–  CLBR 

CLBR 

14A IN9 

BKRL 

JOG

 

BKRL BKRL BKRL BKRL BKRL  BKRL 

15A IN10 

RMOD 

RMOD 

RMOD 

RMOD 

RMOD 

RMOD 

RMOD 

RMOD 

16A IN11 

HOME 

HOME 

HOME 

HOME 

HOME 

– HOME 

HOME 

17A IN12 

*STP 

*STP 

*STP 

*STP 

*STP – *STP 

*STP 

18A IN13 

CSTR 

CSTR/PW

RT 

CSTR CSTR  – 

–  CSTR 

– 

19A IN14 

RES 

RES 

RES 

RES 

RES 

RES 

RES 

RES 

20A IN15 

SON 

SON 

SON 

SON 

SON 

SON 

SON 

SON 

1B 

Output 

OUT0 

PM1 

(ALM1) 

PM1 

(ALM1) 

PM1 

(ALM1) 

PM1 

(ALM1) 

PE0 LS0 

PM1 

(ALM1) 

PE0 

2B OUT1 

PM2 

(ALM2) 

PM2 

(ALM2) 

PM2 

(ALM2) 

PM2 

(ALM2) 

PE1 

LS1 

(TRQS) 

PM2 

(ALM2) 

PE1 

3B OUT2 

PM4 

(ALM4) 

PM4 

(ALM4) 

PM4 

(ALM4) 

PM4 

(ALM4) 

PE2 

LS2 

(Note3)

 

PM4 

(ALM4) 

PE2 

4B OUT3 

PM8 

(ALM8) 

PM8 

(ALM8) 

PM8 

(ALM8) 

PM8 

(ALM8) 

PE3 – 

PM8 

(ALM8) 

PE3 

5B OUT4 

PM16 

PM16 

PM16 

PM16 

PE4 

– 

PM16 

PE4 

6B OUT5 

PM32 

PM32 

PM32 

PM32 

PE5 

– 

TRQS 

TRQS 

7B OUT6 

MOVE 

MOVE 

PM64 

PM64 

PE6 

– LOAD 

LOAD 

8B 

OUT7 

ZONE1 

MODES PM128 PM128 ZONE1 ZONE1 CEND  CEND 

9B OUT8 

PZONE/ 

ZONE2 

PZONE/ 

ZONE1 

PZONE/ 

ZONE1 

PM256 

PZONE/ 

ZONE2 

PZONE/ 

ZONE2 

PZONE/ 

ZONE2 

PZONE/ 

ZONE2 

10B OUT9 

RMDS 

RMDS 

RMDS 

RMDS 

RMDS 

RMDS 

RMDS 

RMDS 

11B OUT10 

HEND 

HEND 

HEND 

HEND 

HEND 

HEND 

HEND 

HEND 

12B OUT11 

PEND 

PEND/ 
WEND 

PEND PEND PEND  –  PEND  PEND 

13B OUT12 

SV 

SV 

SV 

SV 

SV 

SV 

SV 

SV 

14B OUT13 

*EMGS 

*EMGS 

*EMGS 

*EMGS 

*EMGS 

*EMGS 

*EMGS 

*EMGS 

15B OUT14 

*ALM 

*ALM 

*ALM 

*ALM *ALM *ALM  *ALM  *ALM 

16B 

OUT15 

(Note3)

 

LOAD/TRQS 

*ALML 

/*BALM 

*ALML 

/*BALM 

LOAD/TRQS 

*ALML 

/*BALM 

LOAD/TRQS 

*ALML 

/*BALM 

LOAD/TRQS 

*ALML 

/*BALM 

*BALM/ 

*ALML 

*ALML *ALML 

17B 

– 

 

– 

18B 

– 

 

– 

19B 0V 

 

20B 0V 

 

(Note)  “*” in codes above shows the signal of the active low. 

PM1 to PM8 indicate the alarm binary code output signal when an alarm is generated. [Refer to the Instruction Manual 
for the details] 

(Note 1) PIO Patterns 6 and 7 should be available only when PCON-CBP/CGBP are ordered at purchasing. 
(Note 2) The setting can be changed over to PZONE if set in the parameter setting. 
(Note 3) It is invalid before home-return operation. 

(Note 4) *BALM is dedicated for ACON. 

 

PIO Input and Output Interface

 

 

Input section 

Output section 

Speci

fic

atio

Input voltage 

24V DC

10% 

Load voltage 

24V DC 

Input current 

5mA    1 circuit 

Peak load electric 

current 

50mA/1 point 

ON/OFF voltage 

ON voltage  MIN. 18V DC 
OFF voltage  MAX. 6V DC 

Leak Current 

MAX. 2mA/1 point (PCON) 
MAX. 1mA/1 point   

(ACON, DCON) 

NPN 

680

5.6K

P24

External 
Power Supply
24V DC 

Input 
Terminal

Internal 

Power 

Source

Controller

 

15

P24

N

Load

External 
Power Supply
24V DC 

Output 
Terminal

Internal 

Power 

Source

Controller

 

PNP 

680

5.6K

N

External 
Power Supply
24V DC 

Input 
Terminal

Internal 

Power 

Source

Controller

 

15

P24

N

Load

External 
Power Supply
24V DC 

Output 
Terminal

Internal 

Power 

Source

Controller

 

 

 

NPN Specification

 

PNP Specification 

 
 
 
 
 
 
 
 
 
 

I/O Cable 
 Model 

CB-PAC-PIO

□□□

 

 

 

(Enter the cable length (L) in 

□□□

    Example. 020 



2m) 

 
 
 
 
 

 
 
 
 
 
 
 

No.  Signal Name  Cable Color 

Wiring 

No.  Signal Name  Cable Color 

Wiring 

1A 24V  BR-1 

Flat Cable

A

 

(Insulation-Displacement 

Connectors) 

AWG28 

1B OUT0  BR-3 

Flat Cable

B

 

(Insulation-Displacement 

Connectors) 

AWG28 

2A 24V  RD-1 

2B OUT1  RD-3 

3A PP  OR-1 

3B 

OUT2 OR-3 

4A /PP  YW-1 

4B 

OUT3 YW-3 

5A IN0  GN-1 

5B 

OUT4 GN-3 

6A IN1  BL-1 

6B 

OUT5  BL-3 

7A IN2  PL-1 

7B 

OUT6  PL-3 

8A IN3  GY-1 

8B 

OUT7 GY-3 

9A IN4  WT-1 

9B 

OUT8 WT-3 

10A IN5  BK-1 

10B 

OUT9  BK-3 

11A IN6  BR-2 

11B 

OUT10 BR-4 

12A IN7  RD-2 

12B 

OUT11 RD-4 

13A IN8  OR-2 

13B 

OUT12 OR-4 

14A IN9  YW-2 

14B 

OUT13 YW-4 

15A IN10  GN-2 

15B 

OUT14  GN-4 

16A IN11  BL-2 

16B 

OUT15  BL-4 

17A IN12  PL-2 

17B  NP 

PL-4 

18A IN13  GY-2 

18B  /NP  GY-4 

19A IN14  WT-2 

19B  0V 

WT-4 

20A IN15  BK-2 

20B  0V 

BK-4 

 

Loadcell (PCON-CBP/CGBP Dedicated Option)

 

It is a pressing force measurement unit used in the force control. 
It should be used by connecting to an actuator applicable for the force control or servo pressing. 
[Specification] 

Item 

Specification 

Loadcell System 

Strain Gauge 

Rated Capacity [N] 

600 

2000 

Total Accuracy [% F.S.] 

±1 

Allowable Overload [% F.S.] 

200 

Environmental 
Specifications 

Surrounding Air Temperature 

0 to 40 

Surrounding Humidity 

85%RH or less (non-condensing) 

Surrounding Environment 

Should be no corrosive gas 

Surrounding Storage Temperature 

-10 to 60 

Ambient Humidity for Storage 

90%RH less (non-condensing) 

Vibration Resistance 

10 to 57Hz in X, Y and Z directions 

Dielectric Withstanding Voltage [V] 

DC50V 

* F.S.(Withstand Load) 
Note  The number of actuators available to connect should differ depending on the rated capacity of a loadcell.   
[Check in an instruction manual of an actuator for how to install and details of dimensions.]

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Operation in Pulse Train Control Mode   

(function for PLN and PLP Types only) 

Pulse Train Input and Output Interface 

Category  Abbreviated Code 

Signal Name 

Contents of Functions 

Input 

PP, /PP 

Command Pulse Input 

Inputs the command pulse train. 
Input pulse frequency differs depending on the type. 
[Refer to Basic Specifications]

 

NP, /NP 

  When Host Unit is Differential System 

(Although the example shows PCON, it is the same for ACON and DCON.) 

 
 
 
 
 
 
 

 

 

Note1 : Use the same power source (0V) for the host open collector output, AK-04. 

  When Host Unit is Open Collector System [AK-04 (option) is required] 

(Although the example shows PCON, it is the same for ACON and DCON.) 

 

 
 
 
 
 
 
 
 
 
 

 

Note1 : 1) Use the same power source (0V) for the host open collector output, AK-04. 

2) Have the cables as short as possible between the host unit and AK-04. 

 
PIO Pattern 6 ... Pulse Train Control Mode (for incremental type actuators) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
PIO Pattern 7 ... Pulse Train Control Mode (for Absolute type actuators) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
* shows a signal in active low. The input signal should be processed when it turns off, and the output signal should ordinary be 

on while the power is turned on and turns off when the signal gets output. 

 

 

Pin No.

Pin No.

Load

Load

Flat Cable (20-core) 

× 

2

BK-4

BR-3

BK-2

BR-1

No treatment
conducted

No treatment
conducted

20A

20B

1A

1B

Half Pitch MIL Socket
HIF6-40D-1.27R (Hirose Electric)

A

B

L

0V

24V
DC

0V

0V

1

2

3

4

1

2

3

4

PCON

PIO Connector

3A

4A

17B

18B

19B

20B

Host Unit

Positioning Unit

Pulse
Command

0V

0V

PP

/PP

NP

/NP

/PP

PP

NP

/NP

NP

PP

0V

24V

Pulse Converter
AK-04
(to be purchased separately)

24V

PCON

PIO Connector

3A

4A

17B

18B

Host Unit

Positioning Unit

Pulse Command
(Line Driver:
 26C31 or equiv.)

PP

/PP

NP

/NP

0V(NPN Type)

BR- 1

1A P24

PWR 1B

BR- 3

0V

24V DC(NPN Type)

24V DC(PNP Type)

RD- 1

2A

P24

SV 2B

RD- 3

0V(PNP Type)

OR- 1

3A

SON

INP 3B

OR- 3

System Ready

YW- 1

4A

RES

HEND 4B

YW- 3

Servo ON Status

GN- 1

5A

HOME

TLR 5B

GN- 3

BL- 1

6A

TL

6B

BL- 3

PL- 1

7A

CSTP

7B

PL- 3

Deviation Counter Clear

GY- 1

8A

DCLR

8B

GY- 3

Brake Control Release

Compulsory Stop

Torque Limit Select

WT- 1

9A

BKRL

ZONE1
ZONE2

9B

WT- 3

Operation Mode

BK- 1

10A

RMOD

RMDS

10B

BK- 3

Zone 2

Zone 1

Home Return

BR- 2

11A

ALM1
ALM2
ALM4
ALM8

11B

BR- 4

RD- 2

12A

12B

RD- 4

Operating Mode Status

Emergency Stop Status

OR- 2

13A

13B

OR- 4

Home Return Completion
Torque Under Control

Reset

YW- 2

14A

*EMGS

14B

YW- 4

Position Completion

Servo ON

GN- 2

15A

*ALM

15B

GN- 4

BL- 2

16A

16B

BL- 4

PL- 2

17A

N

17B

PL- 4

Alarm Code Output 1

Alarm

Alarm Code Output 2
Alarm Code Output 4
Alarm Code Output 8

GY- 2

18A

N

18B

GY- 4

WT- 2

19A

19B

WT- 4

BK- 2

20A

20B

BK- 4

PCON

 PIO Connector

NC/*ALML

None/Light Error Alarm Output

PP
/PP

NP

/NP

Differential Pulse Supply
[Refer to the next page for
the details of wiring.]

Differential Pulse Supply
[Refer to the next page for
the details of wiring.]

0V(NPN Type)

BR- 1

1A

P24

PWR

1B

BR- 3

0V

24V DC(NPN Type)

24V DC(PNP Type)

RD- 1

2A

P24

SV

2B

RD- 3

0V(PNP Type)

OR- 1

3A

SON

INP

3B

OR- 3

System Ready

YW- 1

4A

RES

HEND

4B

YW- 3

Servo ON Status

GN- 1

5A

HOME

TLR

5B

GN- 3

BL- 1

6A

TL

6B

BL- 3

PL- 1

7A

CSTP

7B

PL- 3

Deviation Counter Clear

GY- 1

8A

DCLR

8B

GY- 3

Brake Control Release

Compulsory Stop

Torque Limit Select

WT- 1

9A

BKRL

ZONE1

REND

ZONE2

9B

WT- 3

Operation Mode

Datum Position Movement Command

BK- 1

10A

RMOD

RSTR

RMDS

10B

BK- 3

Zone 2

Zone 1

Home Return

BR- 2

11A

ALM1
ALM2
ALM4
ALM8

11B

BR- 4

RD- 2

12A

12B

RD- 4

Operating Mode Status

Emergency Stop Status

OR- 2

13A

13B

OR- 4

Home Return Completion
Torque Under Control

Reset

YW- 2

14A

*EMGS

14B

YW- 4

Position Completion

Servo ON

GN- 2

15A

*ALM

15B

GN- 4

BL- 2

16A

16B

BL- 4

PL- 2

17A

N

17B

PL- 4

Alarm Code Output 1

Alarm

Alarm Code Output 2
Alarm Code Output 4
Alarm Code Output 8

GY- 2

18A

N

18B

GY- 4

WT- 2

19A

19B

WT- 4

BK- 2

20A

20B

BK- 4

ACON, DCON

 PIO Connector

NC/*ALML

None/Light Error Alarm Output
Datum Position Movement Complete

PP
/PP

NP

/NP

Differential Pulse Supply
[Refer to the next page for
the details of wiring.]

Differential Pulse Supply
[Refer to the next page for
the details of wiring.]