background image

 

 

5-5 

 

 

3

 

CONNECT PoE ADAPTER

 

 

Connect the Ethernet cable from the enclosure to the Ethernet port labeled PoE adapter. 

Connect one end of the power cord to the adapter. Connect the other end of the power cord to 

a power outlet.  Note that the PoE adapter is not rated for direct outdoor  locations and must be 

mounted within an appropriately rated weatherproof enclosure (not provided). 

 

4

 

GROUNDING 

The gateway enclosure ground stud should be connected to a quality earth ground using at 

minimum 10AWG wire. 

5

 

LIGHTNING PROTECTION 

 

If the gateway is installed in a location with frequent lightning strikes and is located on a roof, 

or other area that is a potential for a lightning strike it is recommended to install a lightning 

arrestor between the antenna and the gateway.  A device similar to L-Com AL6-NMNFBW-9 is 

recommended.   Consult factory for further details. 

Summary of Contents for Smart Plant WX

Page 1: ...IAC 5200 Metcalf Avenue Overland Park KS 66202 USA iac intl com USA Canada 800 334 7431 Main Office 913 384 5511 Smart Plant Remote Monitoring Systems INSTALLATION GUIDE WX Outdoor Gateway...

Page 2: ...ision History Release 1 2022 11 15 IAC Form IAC IG 001 In case of emergencycall 911 For IAC afterhours troubleshootingandservice assistance contact IAC 24 7 CustomerSupportHotline Phone 913 834 5511 O...

Page 3: ...3 1 1 PURPOSE 1 3 1 2 INTENDED AUDIENCE 1 3 1 3 HOW TO USE THIS GUIDE 1 3 2 MOUNTING 2 4 2 1 PERFORMING INSTALLATION 2 4 2 2 MOUNTING STEP ONE 1 2 4 2 3 MOUNTING STEP TWO 2 2 4 3 CONNECT PoE ADAPTER 2...

Page 4: ...TENDED AUDIENCE This guide will be useful for all users of the WX Outdoor Gateway It will guide Operators and Maintenance personnel through mounting connection start up and operation 1 3 HOW TO USE TH...

Page 5: ...ble Electrical codes 2 2 MOUNTING STEP ONE 1 Fix the bracket included in the mounting kit on the bottom of the enclosure with four M6 12 screws 2 3 MOUNTING STEP TWO 2 Position and tighten the pole cl...

Page 6: ...riately rated weatherproof enclosure not provided 4 GROUNDING The gateway enclosure ground stud should be connected to a quality earth ground using at minimum 10AWG wire 5 LIGHTNING PROTECTION If the...

Page 7: ...dio communicationfromWX sensornodes 8 OPERATION The WX gatewayis providedfullyprovisionedandreadyfor operation There is no useradjustmentof settingsrequiredfornormal operation Monitoring of gatewayope...

Page 8: ...teway Installation Guide SmartPlantRemote Monitoring Systems Literature IAC IG 001 Release 1 2022 11 15 IAC 5200 Metcalf Avenue Overland Park KS 66202 USA iac intl com USA Canada 800 334 7431 Main Off...

Reviews: