background image

3

i

PROGRAMMING

USER LIST : To access the user list press SET key once.

0.0 %

to

100.0 %

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID. 
This  parameter  will  decide  the  maximum  output  power  in  %  applied  to 
the load.

0.5

 to 

100.0 Sec.

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID. 
User  can  set  this  value  based  on  process  being  controlled  &  type  of 
output  being  selected.  For  Relay  O/P,  cycle  time  should  be  more  than 
12sec & for SSR O/P, cycle time should  be less than 10sec.

to 

300 Sec.

This parameter will be prompted only if selected control action is PID. It 
defines  how  strongly  the  controller  will  react  to  rate  of  change  of  PV. 
Value of this parameter is automatically set by auto tune function. If set 
to ‘0’, this function will be disabled.

to 

9999 Sec.

This parameter will be prompted only if selected control action is PID. It 
sets the time taken by PID algorithm to remove steady state error. Value 
of this parameter is automatically set by auto tune function. If set to ‘0’, 
this function will be disabled.

0.5 

to 

99.9°C

This parameter will be prompted only if selected control action is PID. It 
sets  proportional  band  over  which  the  output  power  is  adjusted 
depending  upon  the  error  (SV-PV).  Value  of  this  parameter  is 
automatically set by Auto tune function.

CONTROL LIST : To enter in this mode, press SET & DOWN key simultaneously for 3 sec. User can then set the 
following control parameters.

1 to10 

This parameter will be prompted only if selected control action is PID. 
With this parameter  O/P will be Completely OFF after the Set Point + 
Offset Value. If Disable, O/P will act Depending upon the PID Value 
after Set Point achieved.

This parameter is prompted only if output 2 is configured as soak timer. 
Controller  starts  the  execution  of  soak  time  as  per  the  mode  selected. 
Soak timer can be programmed using four different time base in Config. 
List.

(1)

 

Either absolute auxiliary control or as an alarm (High/Low) mode.

(2)

 

Either deviation auxiliary control or as a deviation alarm  mode.

(3)

  As a band alarm(For all above SP2 has to be enable).

This parameter is prompted if SP2 is Enable & output 2 is configured as

SOAK

TIME

SET

POINT 2

CONTROL

SET POINT

---------- 

User  can  change  SP1  value  using  UP/  DOWN  keys.  Holding  the  key,   
will  change  the  value  at  a  faster  rate.  Press  SET  key  to  store  the 
desired value & move on to the next parameter.

User can set ramp rate/min for SP1 (Set Point) to minimize overshoot. 

This parameter will be available only if Enabled in Configuration List. 

RAMP

RATE

Output 2 will be automatically activated /de-activated w.r.t SP1 & HYS.

This parameter is prompted only if Control Logic for Output1 is 
configured for Heat-Cool.

Output 2 will be permanently Activated (ON).

Output 2 will be permanently De-Activated (OFF). 

User has a choice to set different Lock Code via USER LOCK CODE in 
Config. List.

Set this parameter to 15 (Default LOCK CODE) to access Control List.

1 ~ 9999

LOCK
CODE

PROPOR
 TIONAL
  BAND

INTEGRAL
    TIME

DERIV
ATIVE
 TIME

CYCLE
  TIME

OUTPUT
 POWER
   LIMIT

OUTPUT
    OFF

0°C

0°C

Disable

Disable

Auto

1 min.

0

5.0°C

240

60

16.0 sec.

100 %

LSPL ~ HSPL

 0.0 °C
     to
25.0 °C

LSPL ~ HSPL
 -99 to +99°C
    2 to 99°C

 1 Sec to
9999 Hrs.

OP2

MODE

  PARA
METER

  PARA
METER

 LOWER
DISPLAY

 LOWER
DISPLAY

 UPPER
DISPLAY

 UPPER
DISPLAY

RANGE

RANGE

DESCRIPTION

DESCRIPTION

DEFAULT

DEFAULT

OIM Px-X28 V2.0 Page 3 of 9

50 %

 to 

100 %

This parameter will be prompted only if selected control action is PID. 
This parameter allows the User to carry out Auto Tuning function below 
the set point. (If tune offset is set to 50 %, tuning will be carried out at 
50 % of the set point and if set to 100 %, tuning will be carried out at 
100 % of the set point.)

  TUNE
OFFSET

100 %

Summary of Contents for Px-428

Page 1: ...ads v Circuit breaker and appropriate fuses must be used for v The controller must be wired as per wiring diagram it to high voltage surges of extended duration high current power cables Where it is i...

Page 2: ...1 For SP programming 2 To access Control mode 3 To access Configuration mode along with UP key 4 To scroll the parameter to store its value 1 To increase alter parameter value in program mode 2 To ent...

Page 3: ...ed as soak timer Controller starts the execution of soak time as per the mode selected Soak timer can be programmed using four different time base in Config List 1 Either absolute auxiliary control or...

Page 4: ...Output1 is configured for Heat Cool SP set point will be consider as SP Gap1 for heating This parameter will be prompted only if selected control mode for output2 is Auxiliary control or an Alarm The...

Page 5: ...ut is ON PV decreases when output is ON User can select cooling logic in which OP1 will remain ON till PV SP This parameter will be prompted only if selected input is RTD or RTD 1 and is used for BOD...

Page 6: ...vated By pressing DOWN key Lower display will Toggle between SP1 value SP2 value Alarm SP Value AL SP Timer value SOAK By this parameter Lower display will only show the SP1 value By this parameter Lo...

Page 7: ...ompletion of current soak time cycle 1 At every Power ON 3 Power failure during soak time is in progress In this Mode Timer will start only after pressing START key for 3 sec PV SV for any of the foll...

Page 8: ...will Disable Alarm O P at power ON If this parameter is set as NO Alarm condition persists it will Enable Alarm O P at power up Once the Alarm is activated User has following three options to de activ...

Page 9: ...remains OFF till actual temperature drops down in Heat Logic or raises in Cool Logic equal to hysterisis set by user As shown in Fig 3 1 3 2 If the control performance by using auto tuning is still u...

Page 10: ......

Page 11: ......

Page 12: ...remains OFF till actual temperature drops down in Heat Logic or raises in Cool Logic equal to hysterisis set by user As shown in Fig 3 1 3 2 2 Substantial change in SP from previous auto tuning value...

Reviews: