OIM Px-X18

e

 V2.1 Page 4 of 5

LOWER

DISPLAY

UPPER

DISPLAY

 PARA

METER

DESCRIPTION

DEFAULT

CONTROL 

LOGIC

FOR O/P

HEAT

(PV increases when output is ON.)

User can select heating logic in which OP1 will remain ON till PV < SP.

This parameter will be prompted only if selected control mode is ON-OFF. 

This parameter will be prompted only if selected control mode is ON-OFF. 

(PV decreases when output is ON.)

User can select cooling logic in which OP1 will remain ON till PV > SP.

CONTROL 

MODE

FOR O/P 1

PID

User can select between PID or ON-OFF action algorithm to be adopted for output.

INPUT

FILTER

4

Controller  is  equipped  with  an  adaptive  digital  filter  which  is  used  to  filter  out  any 
extraneous  pulses  on  the  PV.  Filtered  PV  Value  is  used  for  all  PV  dependent 
functions.  If  PV  signal  is  fluctuating  due  to  noise,  increase  the  filter  time  constant 
value.

PROCESS 

VALUE

OFFSET

o

0  C

(ii) To match the display values with another recorder or indicator measuring the  

(i) To compensate for known thermal gradient.

     same PV.

Function of this parameter is to add/subtract a constant value to the measured PV to 
obtain Final PV for control applications. This parameter value needs to be altered for 
one of the following reason : 

LOWER

SET

POINT

LIMIT

o

0  C

Sets  the  minimum  limit  for  set  point  adjustment.  It  can  be  set  from  minimum 
specified range of selected sensor to HSPL value.

HIGHER

SET

POINT

LIMIT

o

400  C

Sets  the  maximum  limit  for  set  point  adjustment.  It  can  be  set  from  LSPL  value  to 
maximum specified range of selected sensor.

OUTPUT                 

TYPE

RELAY

Select  Relay  if  LOAD  is  connected  via  contactor.  Whenever  user  selects  Relay,  Cycle 
time will automatically get set to 16 sec. User can modify cycle time via control list.

User  has  to  set  this  parameter  very  carefully  in  accordance  with  the  output  used. 
(Separate terminal for RELAY & SSR, Refer  electrical installation )

Select  SSR  if  LOAD  is  connected  via  SSR  (DC  voltage  pulses).  Whenever  user 
selects    SSR,  Cycle  time  will  automatically  get  set  to  1sec.  User  can  modify  cycle 
time via control list.

OVERSHOOT

CONTROL

POINT

DISABLE

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID.  Setting  this 
parameter  on  higher  side  will  proportionally  slows  down  the  rate  of  rise  of  PV  to 
minimize  overshoot(this  may  cause  delay  to  reach  SP).  Setting  on  lower  side  will 
proportionally or disabling this parameter will increase the rate of rise of PV( which 
may cause overshoot). Disable this option if delay is not required to reach SP.

15

Default USER LOCK CODE is 15 to access Control & Configuration List.
User has a choice to set its own USER LOCK CODE between 1 to 9999, this is to 
prevent unauthorized access of Control & Configuration List. 

USER 
LOCK 
CODE

AUTO

TUNE

Enable

If Disabled, this parameter will not be prompted if user press Up & Down keys 
Simultaneously for 3Sec. 

SET

POINT 1

Enable

If Enabled, User can View & edit the Set point in USER list. 

If disabled, User can only View the Set Point but Can not edit it in USER list.

This parameter will be prompted only if selected control action is PID. 
If  Enabled,  this  parameter  will  be  prompted  if  user  press  Up  &  Down  keys 
Simultaneously for 3Sec. 

RAMP

RATE

Disable

This parameter will be prompted only if OCP (over shoot control point) is disabled.
When enabled, User can set the desired RAMP rate in USER list.

When disabled, this parameter will not be prompted in USER list.