Gemini Instruction Manual I-GARD
7
The factory default settings are as shown in Table 1.
Table 1 GFR-RM DeFaulT SeTTinGS
FunCTiOn
SeTTinG
SWiTCH nO
.
DiReCTiOn
MODE
NON FAILSAFE
1
DOWN
MEMORY ON
2
DOWN
DELAY
60mS
3
DOWN
4
DOWN
5
DOWN
6
DOWN
7
DOWN
LEVEL
50% IGMAX
8
UP
9
UP
10
UP
CURRENT
5A, 1000:1 CT
1
DOWN
2
DOWN
3
DOWN
4
DOWN
5
DOWN
6
DOWN
Figure 6 GFR-RM Dipswitch
4
MAINTENANCE
Gemini
is designed and constructed to operate properly with minimal maintenance, however
,
it is recommended
that it be tested on a regular basis at a
minimum
of once every six months. The self-test feature allows for a
rapid and reliable test.
MODE
DELAY
LEVEL
CURRENT
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6
G/F TRIP SET
NGR SET