C-415EM 

 

INSTRUCTION MANUAL 

DSP-CA(S) CABLE ADAPTER

 

 

April 2007 

 

 

 

 

Figure 2.2 Modular Jack connections 

 

On the modular jack the pin-out connections are in the same order as for the terminal block assignment. i.e. 
Pin 1 signal is TRIP SIGNAL 
Pin2 signal is FEEDER ALARM 
Pin 3 signal is P0 
Pin 4 signal is P1 
Pin 5 signal is P2 
Pin 6 signal is P3 
Pin 7and Pin 8 is GND 
 
Pin 7 or 8 can be used to connect the shield of a cable to ground at one end only . 
 
The connection should be the same at both ends of the cable i.e. pin 1 of one plug should connect to pin 1 on the 
other plug and pin 2 to pin 2, and so on.  
 
 
3. Testing 
 

3.1.  A digital multimeter can be used to to verify that the connection is working. With the DSP energized, 

connect a digital meter set to read ohms or continuity, between terminal 13 on the left side adapter (whether 
it be DSP-CA or DSP-CAS does not matter) and terminal 13 on the right side adapter. There should be no 
continuity (2 Megohms, or greater) when there is no short across terminals 1 and 2 of the DSP-CAS and 
when shorted there should be low resistance between the two terminals (less than 100 ohms). Repeat for 
the other terminals 14 to 18.  

 

 
 
 

www 

. ElectricalPartManuals 

. com

Summary of Contents for DSP-CA

Page 1: ...ssory DSP CA S Cable Adapter Instruction Manual 7615 Kimbel Street Mississauga Ontario Canada L5S 1A8 Tel 905 673 1553 Fax 905 673 8472 Toll Free 1 888 RESISTR 737 4787 www i gard com w w w E l e c t...

Page 2: ...To prioritize the combined system it is possible to join the two priority buses together when the tie breaker is closed using an 8 conductor shielded cable The cable can connected at either end throug...

Page 3: ...ectors from either side as desired See Figure 2 1 a and b 2 2 Terminal 13 should connect to terminal 13 on both sides of the board in a double ended situation terminal 14 to terminal 14 etc for 7 cond...

Page 4: ...arm P 0 P 1 P 2 P 3 Gnd Gnd Ribbon to DSP DFM Figure 2 1 a DSP CAS Connections Figure 2 1 b DSP CA Connections 1 2 13 14 15 16 17 18 19 20 ON DSP CAS Trip Signal Feeder Alarm P 0 P 1 P 2 P 3 Gnd Gnd R...

Page 5: ...e i e pin 1 of one plug should connect to pin 1 on the other plug and pin 2 to pin 2 and so on 3 Testing 3 1 A digital multimeter can be used to to verify that the connection is working With the DSP e...

Page 6: ...SP CA and DSP CAS 58 00mm 8 5 00m m 70mm Figure 4 1 Dimensional Details DSP CA S 5 Typical Installation Diagrams 5 1 Figures 5 1 and 5 2 illustrate the use of the DSP systems in double and triple ende...

Page 7: ...Typical Main Tie Main Substation with two DSP systems DSP CAS Switch DSP CA No Switch N O Contact Screw Terminals or RJ 45 Jack Shielded Cable 22 Gauge x 8 conductor Shield Connected to Ground at one...

Page 8: ...ABLE ADAPTER April 2007 8 DSP CAS Switch DSP CA DSP CAS Switch DSP CA AuxContact DSP CAS Switch AuxContact Figure 5 2 Typical Main Tie Main Tie Main Substation with three DSP systems w w w E l e c t r...

Page 9: ...673 1553 7615 Kimbel St Unit 1 FAX 905 673 8472 Mississauga ON e mail info i gard com L5S 1A8 Website www i gard com QUALITY PRODUCTS TECHNICAL EXCELLENCE PREMIUM SERVICE w w w E l e c t r i c a l P...

Reviews: