I-Gard DSP-CA Instruction Manual Download Page 2

C-415EM 

 

INSTRUCTION MANUAL 

DSP-CA(S) CABLE ADAPTER

 

 

April 2007 

 

 

 

 
 

 
1. Introduction 
 

1.1.  The DIN –Rail mounted DSP Ground Fault Protection system from IPC Resistors is used exclusively with 

High-Resistance Grounded (HRG) power systems. The DSP can be used on multi-source substations such 
as double-ended main-tie-main board arrangements. In the case of a utility outage on one of the sources of 
such a system, the main breaker on one side will open and the tie breaker will close (through key interlock 
or other controls) so that power on the ‘dead’ side is supplied from the ‘live’ side to maintain service to both 
sides of the board.  

 
1.2.  The DSP system includes priority allocation to each feeder breaker depending on its importance. On a 

double-ended station there will be two DSP systems – one on each side of the board. Normally they will 
operate independently of each other. However, when the tie breaker is closed the two DSP systems will not 
prioritize breakers on the other side of the board and in the event of a fault involving both sides of the board, 
then two breakers would trip.  

 
1.3.  To prioritize the combined system it is possible to join the two priority buses together when the tie breaker is 

closed using an 8-conductor shielded cable. The cable can connected at either end through IPC cable 
adapter modules types DSP-CA or DSP-CAS.  

 
1.4.  The DSP-CA and DSP-CAS are similar 70mm DIN rail mounted units that tie into the DSP system with 

standard 20 position ribbon cable connectors (IPC Resistors RC-3) the 8-conductor cable then may be 
connected to either an 8-position terminal block or plugged into a RJ-45 8-8 Modular Jack at the discretion 
of the installer. The DSP-CA and DSP-CAS modules simply act as junction boxes to connect the priority bus 
lines to the appropriate ribbon cable terminals. 

 
1.5.  The DSP-CAS includes an electronic switch to connect or disconnect the priority bus from the DSP bus. 

This switch is controlled by a contact closure across the two input terminals (1 and 2). A yellow ON LED 
indicates that the switch is activated. 

 
1.6.  The DSP-CA module is simply a junction box without switching. One of each module is required to interface 

the cable to the DSP Modules.  

 

Note: A DSP-CAS can be used instead of a DSP-CA if necessary, but the input terminals would have to be 
permanently shorted

.  

 
 
 
 
 
 
 
 
 
 
 

www 

. ElectricalPartManuals 

. com

Summary of Contents for DSP-CA

Page 1: ...ssory DSP CA S Cable Adapter Instruction Manual 7615 Kimbel Street Mississauga Ontario Canada L5S 1A8 Tel 905 673 1553 Fax 905 673 8472 Toll Free 1 888 RESISTR 737 4787 www i gard com w w w E l e c t...

Page 2: ...To prioritize the combined system it is possible to join the two priority buses together when the tie breaker is closed using an 8 conductor shielded cable The cable can connected at either end throug...

Page 3: ...ectors from either side as desired See Figure 2 1 a and b 2 2 Terminal 13 should connect to terminal 13 on both sides of the board in a double ended situation terminal 14 to terminal 14 etc for 7 cond...

Page 4: ...arm P 0 P 1 P 2 P 3 Gnd Gnd Ribbon to DSP DFM Figure 2 1 a DSP CAS Connections Figure 2 1 b DSP CA Connections 1 2 13 14 15 16 17 18 19 20 ON DSP CAS Trip Signal Feeder Alarm P 0 P 1 P 2 P 3 Gnd Gnd R...

Page 5: ...e i e pin 1 of one plug should connect to pin 1 on the other plug and pin 2 to pin 2 and so on 3 Testing 3 1 A digital multimeter can be used to to verify that the connection is working With the DSP e...

Page 6: ...SP CA and DSP CAS 58 00mm 8 5 00m m 70mm Figure 4 1 Dimensional Details DSP CA S 5 Typical Installation Diagrams 5 1 Figures 5 1 and 5 2 illustrate the use of the DSP systems in double and triple ende...

Page 7: ...Typical Main Tie Main Substation with two DSP systems DSP CAS Switch DSP CA No Switch N O Contact Screw Terminals or RJ 45 Jack Shielded Cable 22 Gauge x 8 conductor Shield Connected to Ground at one...

Page 8: ...ABLE ADAPTER April 2007 8 DSP CAS Switch DSP CA DSP CAS Switch DSP CA AuxContact DSP CAS Switch AuxContact Figure 5 2 Typical Main Tie Main Tie Main Substation with three DSP systems w w w E l e c t r...

Page 9: ...673 1553 7615 Kimbel St Unit 1 FAX 905 673 8472 Mississauga ON e mail info i gard com L5S 1A8 Website www i gard com QUALITY PRODUCTS TECHNICAL EXCELLENCE PREMIUM SERVICE w w w E l e c t r i c a l P...

Reviews: