ADJUSTING CONTROL STOP

Step 1

Turn adjustment screw 

COUNTERCLOCKWISE

 1/2 turn from 

closed position. Activate flush valve.

Step 2

To adjust flush valve, turn adjustment screw in small increments. 

Activate flush valve after each adjustment. The proper flow rate 

should completely cleanse fixture without splashing water 

outside of fixture.

NOTE:

 The flow from the valve must never exceed the flow 

capacity of the fixture. If a valve failure should occur, the fixture 

must be able to accommodate a continuous flow from the valve.

Step 3

Reinstall control stop cap.

CONTROL MODULE AND INTERFACE SETUP

NOTE:

 When powered and face plate is removed, control module 

automatically enters maintenance mode. While maintenance 

mode is active, a solid green light indicates that a user is 

 

detected. Control module exits maintenance mode when face 

plate is replaced or after 30 minutes. To re-enter maintenance 

mode, press any quick action button.

QUICK ACTION BUTTON DIAGRAM

Full Flush

Half Flush

Summary of Contents for COBALT Pro 101675

Page 1: ...ommercial manufactured products are made of first class materials are free from defects and are made to withstand normal use when installed properly Products have the following warranty periods 3 year...

Page 2: ...x 4 x 4 x 2 1 2 The location will vary based on the rough in Refer to the rough in drawings for specific mounting location Use a GFCI plaster ring 4X4 JUNCTION BOX GFCI PLASTER RING I CON IR PLATE AN...

Page 3: ...com patents Part No 101675 page 3 Rev 080323 Step 5 Install actuator cover ProLAST T SEAL FLUSH VALVE CAP ASSEMBLY INSTALLATION Step 1 Insert ProLAST T Seal into flush valve body Step 2 Place square...

Page 4: ...rough junction box knock out Attach control module to junction box with provided screws Step 3 Reattach and secure cover with set screw WALL SENSOR INSTALLATION INSTALLATION WITHOUT ELECTRICAL BOX Ste...

Page 5: ...g out then up Step 4 Feed control module cable through 1 1 2 opening Attach control module to wall with provided screws Step 5 Reattach and secure face plate with set screw MOUNTING WALL FLANGE Step 1...

Page 6: ...eed the cable through the wall Step 4 Attach the wall flange to the wall using the screws provided Lock the conduit in place using the set screw on the wall flange INTERFACE MODULE INSTALLATION Step 1...

Page 7: ...ve after each adjustment The proper flow rate should completely cleanse fixture without splashing water outside of fixture NOTE The flow from the valve must never exceed the flow capacity of the fixtu...

Page 8: ...e quick action button Current profile number is displayed through LED illuminations and the digital display To change profile press and release profile quick action button again Continue to press and...

Page 9: ...ser The range can be adjusted from 6 54 inches Exit adjusts the amount of time an object must not be detected before the valve considers the user to have exited The range can be adjusted from 0 15 sec...

Reviews: