COBALT Essential

 Sensor Faucet 

Standard Operations

102664

I-CON  Systems,  Inc.,  for  product  support  call  1-866-730-7192  or  visit  us  online  at  support.i-con.com                           

One or more products contained herein are protected by U.S. Patent with other undergoing the patent process www.i-con.com/patents

  ACTIVATION

page 1

Rev 081023

To prevent flooding activations will stop after 30 seconds. 

AUTO ACTIVATION

The faucet will automatically activate based on IR detection. The IR sensor has 3 LEDs, a red, green, and blue to indicate detection 

and activation status. 

When no object is detected no LED indication will be displayed. 

During object detection the faucet will blink a green LED in 5-second intervals. If the faucet is powered by a plug-in transformer 

 

a solid blue LED will also illuminate. 

MANUAL ACTIVATION

Press the activate button on the control module, this will toggle the water on and off. 

SENTINEL ACTIVATION

Sentinel activation will automatically activate the faucet 24 hours after the last activation, by default sentinel activation is off. 

 

To toggle this feature, hold down the activate button for 5 seconds The red LED located in the IR sensor window will stay on 

 

for 3 seconds to indicate it has been turned on, or blink for 3 seconds if it has been turned off. 

ACTIVATION REFUSAL

When an activation is attempted but the device is in a state of end-of-life battery, obstruction, or disabled, a red LED will flash, 

 

and the faucet will not activate. 

  ALERTS

Alerts are indicated by a red LED flashing every 10 seconds.

OBSTRUCTION

When an object has remained detected for 30 minutes auto activations will be disabled. To reset an obstruction alert, the faucet 

must not detect anything for at least 5 seconds. 

Activations cannot last more than 30 seconds. An obstruction will not cause your faucet to run continuously. 

LOW BATTERY

When the battery voltage has dropped below 6V. 

BATTERY END-OF-LIFE

When the battery voltage has dropped below 5V. If the faucet is running only on battery power activations will be disabled 

 

and the red LED will flash rapidly. 