7. TECHNICAL DATA
87
NOTE!
The rated currents in given ambient temperatures (in Table 36 The technical data of the N800A AC drive) are
achieved only when the switching frequency
≤
the factory default.
If your process includes a cyclical load, for example if there are lifts or winches, speak to the manufacturer to get
the dimensioning information.
7.1.3 OVERLOAD CAPABILITY
The
low overload
means that if 110% of the rated continuous current (I
L
) is required for 1 minute every 10 minutes, the remaining
9 minutes must be approximately 98% of I
L
or less.
This is to make sure that the output current is not more than I
L
during the duty cycle.
Fig. 31: Low overload in N800A
The
high overload
means that if 150% of the rated continuous current (I
H
) is required for 1 minute every 10 minutes, the re-
maining 9 minutes must be approximately 92% of I
H
or less.
This is to make sure that the output current is not more than I
H
during the duty cycle.
N800A
Summary of Contents for N800 Series
Page 2: ...ISSUEDATE 2015 06 26 VER 1 ...
Page 3: ......
Page 19: ...3 MOUNTING 3 2 2 WALL MOUNTING OF MR5 Fig 3 ThedimensionsoftheACdrive MR5 13 N800A ...
Page 20: ...3 MOUNTING 3 2 3 WALL MOUNTING OF MR6 Fig 4 ThedimensionsoftheACdrive MR6 14 N800A ...
Page 21: ...3 MOUNTING 3 2 4 WALL MOUNTING OF MR7 Fig 5 ThedimensionsoftheACdrive MR7 15 N800A ...
Page 23: ...3 MOUNTING 3 2 6 WALL MOUNTING OF MR8 IP00 Fig 7 ThedimensionsoftheACdrive MR8 IP00 17 N800A ...
Page 52: ...4 POWERCABLING 46 3 Removethecablecover MR8 MR9 N800A ...
Page 53: ...4 POWERCABLING 47 4 Removethecableentryplate MR8 MR9 N800A ...
Page 54: ...4 POWERCABLING 48 5 MR9only Loosenthescrewsandremovethesealingplate N800A ...
Page 55: ...4 POWERCABLING 49 6 RemovetheEMCshieldplate A ThewingnutinMR8 A MR9 N800A ...
Page 80: ...5 CONTROLUNIT 74 Fig 30 Thegalvanicisolationbarriers A Thecontrolunit B Thepowerunit N800A ...
Page 101: ......