The minimum distance between a module frame and a sidewall of clamp for linear thermal expansion 
of the module frame supports should be 2.5mm, in order to reduce pressure loads. 

·

 

All the junctions on the conductive connection must be fixed. Metal containing iron in the conductive 
connection should be made with stainless steel or be treated against corrosion by anodizing, spray-
painting, or galvanization to prevent rusting and corrosion. 

·

 

Modules that feature antireflective coated glass are prone to visible finger print marks if touched on 
the front glass surface. HHI recommends handing modules with anti-reflective glass with gloves or 
limiting touching of the front surface. Any finger print marks resulting from installation will naturally 
disappear over time or can be reduced by following the washing guidelines in Section 7.1. 

 

3.3   General Operation Condition 

PV modules will be operated under General Operation Condition (GOC). Do not install PV module at 
site beyond General Operation Conditions or under specific condition. 

 

1)  General Operation Conditions 

The site condition for the sea level and wind load should be matched the following requirements. 

 

(1) Sea level of site : Below 1,000m (3,280ft) 

 

(2) Maximum Instantaneous wind Speed 

·

 

Below 5,400Pa (5,400N/m

2

, 550kg/m

2

,

 

112lb/ft

2

) on the front module surface 

·

 

Below 2,400Pa (2,400N/m

2

, 225kg/m

2

,

 

46lb/ft

2

) on the back module surface 

 

 

If the wind strength is not over than 2,400Pa (2,400N/m

2

, 225kg/m

2

,

 

4 lb/ft

2

), the installation site 

over 1,000m (3,280ft) above sea level is permitted. 

 

Installations under the condition of wind strength specified above are allowed only when the 
methods of installations comply with Module Installation Instruction (Appendix 1.) 

 

2)  Specific Site Condition 

(1) Actual site condition should be checked for adequate installations. 

1) Chloride is an important factor to be considered. 
2) Hail, heavy snow, and sand are important factors to be considered. 
3) Air pollution, chemical gas, acid rain, and smoke are important factors to be considered. 

 

(2) Environmental conditions. 

1) PV modules shall not be installed in salty area within 500m from a body of salt water and/or area 
where salty wind hit directly. 

 

 

HYUNDAI modules have passed the IEC61701 test (Salt Mist Corrosion Test) 

 

2) PV modules shall not be immersed in water and shall not be continually exposure to Water from a 
sprinkler, fountain, etc. 
3) PV modules shall not be installed in sulfurous area near sulfurous volcano and sulfurous spring. 

 

Summary of Contents for HiS-MxxxMF

Page 1: ...egions may have different regulations for solar PV installations In this manual hereafter IEC only is used to refer to regions where IEC standard applies e g Europe Middle East most of Asia Pacific countries UL only is used to refer to regions where UL standard applies e g United States Canada all other references are global 2 General Information This manual provides the installation information f...

Page 2: ... directly to sunlight without connection each module generates over DC 30V which is potentially hazardous Modules are heavy Be sure to have more than two persons with anti slip gloves on carry each PV module Do not throw and drop PV modules Do not sit stand step walk and or jump on the module including the frames Do not drop or place objects on the modules Do not place excessive loads on the modul...

Page 3: ...ons for all other components within the total system 3 Installation 3 1 General Before installing and operating HHI PV system installer and operator should follow the requirements specified in this manual Do not drill additional holes in the frame of the modules This additional hole will void the warranty Refer to the mounting profile in Picture1 Picture2 Secure the module using mounting holes pro...

Page 4: ...n 1 General Operation Conditions The site condition for the sea level and wind load should be matched the following requirements 1 Sea level of site Below 1 000m 3 280ft 2 Maximum Instantaneous wind Speed Below 5 400Pa 5 400N m2 550kg m2 112lb ft2 on the front module surface Below 2 400Pa 2 400N m2 225kg m2 46lb ft2 on the back module surface If the wind strength is not over than 2 400Pa 2 400N m2...

Page 5: ...he most outer mounting holes If additional wind loads are anticipated for this installation additional mounting points should be used System designer and installer are responsible for load calculations and for proper design of support structure When installing modules in snowy area additional clamping or supporting parts should be attached to the middle of the lower long side frame to prevent poss...

Page 6: ...f 16 Sales Office 2nd Fl Hyundai Bldg 75 Yulgok ro Jongno gu Seoul 110 793 Korea Factory 313 Soi ro Soi myeon Eumseong gun Chungcheongbuk do 369 872 Korea Picture 2 HiS MxxxMG Hole Position Picture 3 Installation Method using bolt nut ...

Page 7: ...7 of 16 Sales Office 2nd Fl Hyundai Bldg 75 Yulgok ro Jongno gu Seoul 110 793 Korea Factory 313 Soi ro Soi myeon Eumseong gun Chungcheongbuk do 369 872 Korea Picture 4 Mounting Hardware Picture 5 Installation Method using clamping ...

Page 8: ...nt of Isc K 0 056 Output tolerance 3 0 Maximum system voltage Vdc 1 000 IEC 600 UL Cell quantity in series pcs 54 Bypass diodes pcs 3 Cell Type 6inches Multi crystalline Silicon Cell Safety Qualification Class IEC 61215 Class II Maximum Series Fuse Rating A 15 Fire Class rating Class C Electrical Characteristics HiS SxxxMF Mono Crystalline Si Type 3 Bus Bar Type 54 Cells Item HiS SxxxMF xxx Normal...

Page 9: ...ntity in series pcs 60 Bypass diodes pcs 3 Cell Type 6inches Multi crystalline Silicon Cell Safety Qualification Class IEC 61215 Class II Maximum Series Fuse Rating A 15 Fire Class rating Class C Electrical Characteristics HiS SxxxMG Mono Crystalline Si Type 3 Bus Bar Type 60 Cells Item HiS SxxxMG xxx Normal Power Value Normal Power Pmax 250 253 255 258 260 263 265 Voltage at Pmax Vmpp 30 5 30 5 3...

Page 10: ...ide This can resist nominal load on the module surface of 5 400Pa 5 400N m2 550kg m2 112lb ft2 at maximum 5 Wiring 5 1 General All wiring should be matched with proper electrical codes NEC USA or CEC Canada All wiring work should be done by a certified and authorized engineer All wiring should be connected safely in order to prevent any hazard All PV modules for one serial connection must be ident...

Page 11: ... To prevent electric shock and fire an earthing must be done on the frames of PV modules and array The array frame must be earthed according to NEC Article 250 USA or CEC Canada There is an earthing hole in the module frame by using these holes an earth conductor and the module frame must be connected and earthed See picture 6 Picture 6 Grounding Hardware 1 Grounding using Lay in Lug It is necessa...

Page 12: ...40 C 85 C 3 Wire Size 4 0mm2 AWG 12 4 The cable must not be bent or crushed on the direct exit of the cable screw joint A minimum bending radius R 5 x cable diameter must be maintained The cable must be routed in a way that tensile stress on the conductor or connections is prevented Picture 8 Cable Routing 5 7 Conduit For conduit application it is necessary to follow the regulation for outdoor ins...

Page 13: ...s surface only with no heated water only Normal water pressure is more than adequate Do not use harsh cleaning materials such as scouring powder steel wool scrapers blades or other sharp instruments to clean the glass surface of the module Use of such materials or cleaning without consultation will invalidate the product warranty PV modules that are mounted flat should be cleaned more often as the...

Page 14: ...d Fl Hyundai Bldg 75 Yulgok ro Jongno gu Seoul 110 793 Korea Factory 313 Soi ro Soi myeon Eumseong gun Chungcheongbuk do 369 872 Korea Picture 9 Standard module Layout Ground position HiS MxxxMF Picture 10 Standard module Layout Ground position HiS MxxxMG ...

Page 15: ...hi green com solar Page 15 of 16 Sales Office 2nd Fl Hyundai Bldg 75 Yulgok ro Jongno gu Seoul 110 793 Korea Factory 313 Soi ro Soi myeon Eumseong gun Chungcheongbuk do 369 872 Korea Picture 11 Junction box ...

Page 16: ...ibed in Hyundai Heavy Industries installation Manual are covered by 2 400Pa Warranty Method 2400 Pa 5400 Pa Bolting Long Bar Clamping Clamping area Additional support bar area Additional Clamping area for slipping snow Long Bar Clamping Area L 4 L 8 Clamping Area L 4 Short Bar Clamping Area S 4 S 8 Clamping Area S 4 Note 1 The certified mounting method is bolting method by TÜV Rheinland 2 The Moun...

Reviews: