Mechanical Characteristics (HiS-MxxxMF/HiS-SxxxMF)
Description
HiS-MxxxMF/HiS-SxxxMF
Length, mm(inches)
1,476 (58.1)
Width, mm(inches)
983 (38.7)
Depth, mm(inches)
35 (1.38)
Weight, kg(pounds)
16.5 (36.6)
·
Mechanical Characteristics (HiS-MxxxMG/HiS-SxxxMG)
Description
HiS-MxxxMG/HiS-SxxxMG
Length, mm(inches)
1,645(64.7)
Width, mm(inches)
983(38.7)
Depth, mm(inches)
35 (1.38)
Weight, kg(pounds)
18.5(40.8)
·
The specifications in the datasheet is tested under STC conditions.
4.2 Mechanical Loading
As the picture1, picture2 shows, a PV module has 2 mounting holes and 2 NOT USED HOLE at each
side, a total of 8 holes. Please select outside mounting holes at each side. This can resist nominal load
on the module surface of 5,400Pa (5,400N/m2, 550kg/m2, 112lb/ft2) at maximum.
5. Wiring
5.1 General
·
All wiring should be matched with proper electrical codes, NEC (USA) or CEC (Canada).
·
All wiring work should be done by a certified and authorized engineer.
·
All wiring should be connected safely in order to prevent any hazard.
·
All PV modules for one serial connection must be identical in terms of output, in types and
manufacturer of solar cells.
·
Do not connect PV modules directly in parallel without the junction box.
5.2 Module Wiring
·
Maximum system voltage should not exceed 1000[V].
·
The maximum number of modules in parallel connection depends on inverter’s capacity.
·
PV modules are not designed to be connected to load directly. Therefore, a proper inverter must be
connected.
·
Bypass diodes are installed on the modules at the factory. Wrong connection may cause damage to
the bypass diodes, cable and junction box.
·
Fuse rating : Use 15A max series fuse. Fuse capacitance is calculated by using Isc×1.56.