Special photocell to measure and differentiate natural light from LED light from behind the fixture cover
Photocell Advance
DIP switch offers multiple current selections for different luminaire requirements
5-Year Warranty
Ambient daylight
threshold
One-touch daylight learning via remote control
Input current
Input power
0.17 - 0.16A
35W
20s
Warming-up
0s / 10s / 30min / +∞
10% / 30%
Stand-by period
Stand-by dimming level
Sensor OFF / 50% / 75% / 100%
Daylight threshold
Hold time
Sensitivity
Setting adjustments:
5s ~ 10min (selectable)
5 ~ 50 lux, disabled
Tri-level dimming control based upon occupancy (also known as corridor function)
Easy-on-the-eye operation which makes the light turning on/off less uncomfortable
TM
HEC7030
Detached Version with Daylight Mornitoring and Photocell Advance
TM
SensorDIM
TM
- Integrated HF Sensor and LED Driver
Applications
Occupancy sensor and constant current LED driver, 2-in-1.
Suitable for building into the fixture for:
Office / Commercial Lighting
Classroom
Meeting Room
Use for retrofit and new luminaire designs/installations
Features
IP20
RED
EMC standard (EMC)
Safety standard (LVD)
Abnormal protection
Certification
Dielectric strength
EN55015, EN61547, EN6100-2/3
Output short-circuit protection
Semko, CB, CE , EMC, RED, RCM
EN61347-1, EN61347-2-13
Input
→
output: 3750VAC / 5mA /1min
Technical Data
Input Characteristics
Safety and EMC
Off load voltage
Power factor
Efficiency
Output current
350/500/550/700/750/900mA
70V
85% (Max.)
>0.9
Driver Data
Tc: +75
O
C
Operation temperature
Case temperature (Max.)
Ta: -20
O
C ~ +50
O
C
Environment
IP20
IP rating
Sensor Data
Model No.
30
O
~ 150
O
<0.2mW
5.8GHz +/- 75MHz
High Frequency (microwave)
Sensor principle
Operation frequency
Transmission power
Detection range
Detection angle
Max. (
O
x H) 8m x 5m
Model No.
220~240VAC 50/60Hz
Mains voltage
HEC7030
HEC7030
24 hour daylight monitoring dawn/dusk sensor
Daylight
Monitoring
Subject to change without notice.
Edition: 26 Feb. 2020 Ver. A0 Page 1/8