background image

7.Descriptions of the 
Button Functions 
(remote control HRC-11)

Scene prog. [ zone      ] (One-key-commissioning)

1. Press button “Start” to program.
2. Select the buttons in      “Detection range”,     /     “Daylight threshold”, 
        “Hold time”,      “Stand-by time”,      “Stand-by dimming level” to   
    set all parameters.
3. Press button “Memory” to save all the settings programmed in the 
    remote control.
4. Press button “Apply” to set the settings to each sensor unit(s).     
    For example, to pre-set detection range 100%, daylight threshold
    Disable, hold time 5min, stand-by time +∞, stand-by dimming level 
    30%, the steps should be as follows:
    Press button     Start, button     100%,     Disable,     Shift,     5min,        
         Shift,     +∞ ,     30%,     Memory. By pointing to the sensor unit(s)   
    and pressing     Apply, all settings are passed on the sensor(s).

8

8

8

8

3

3

9

9

10 11

11

12

14

13

12

13

14

Brig/- [ button     ]

Press button     to adjust the light brightness to reset the target lux level. 

7

7

Sensor off [ button 

   

 ] (Daylight harvest without occupancy)

1. Press button     , the red LED is on for indication.
2. Press button “Sensor off”, the function of movement detection is
    disabled.
Note: the function of “Twilight” is disabled.          

5

3

Power output [ button 

   

 ]

Press button     , the light output shifts between 80% and 100%.       

6

6

RESET[ button     ]

Press button     , all settings go back to the rotary switch settings. 

2

2

Shift [ button 

    

 ]

Press button     , the LED on the top left corner is on for indication.    
All values / settings in RED are in valid for 20 seconds. 

3

3

Auto Mode [ button     ]

Press button     to initiate automatic mode. The sensor starts working
and all settings remain as before the light was switched ON/OFF.
Note: the function of Semi-auto is disabled.

4

4

Permanent ON/OFF [               ]

Press button     , to select permanent ON or permanent OFF mode.
* Press button     /     to resume automatic operation.
The mode will change to AUTO Mode after power failure.  

button 

1

1

2

4

Detection range [ zone     ] 

Press buttons in zone 

   

  to set detection range at 100% / 75% / 

50% / 10%.

9

9

HIM32-20190104-A1

Hytronik Industrial Ltd.  |  www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai'gang road south, 
Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020   Fax: 86-752-2777877  

1

2

3

Ambient daylight threshold [ button 

    

 ]

1. Press button     Shift, the red LED is on for indication. 
2. Press button 

    

, the ambient lux level is sampled and set as 

    daylight threshold / target Lux level.

3

11

11

Daylight threshold [ zone 

   

  ]          

Press buttons in zone     to set the daylight sensor at 50Lux / 100Lux 
/ 300Lux / 500Lux or Disable as threshold / target Lux level.
Note: 2Lux / 10Lux are disabled.
         To set daylight sensor at 100Lux / 300 Lux / 500Lux, press 
         button     Shift at first.

10

10

3

Hold time [ zone     ]

Press buttons in zone     to set the hold time at 2s / 30s / 1min / 
5min / 10min / 15min / 20min / 30min.
Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button 
                Shift at first.
         2. 2s is for testing purpose only, stand-by period and daylight     
             sensor settings are disabled in this mode.
*To exit from Test mode, press button     or any button in zone     .

3

12

12

12

2

 All buttons in zone      are disabled. 

16

 RF mode [ zone     ]

16

 Dual tech [ zone     ]

15

     Press buttons in zone     to select sensor technology.
     HF+PIR: Light is on when both HF and PIR sensors are activated.
     HF/PIR: Light is on when HF or PIR sensors are activated.

15

Stand-by time [ zone     ]

Press buttons in zone     to set the stand-by period at 0s / 10s / 
1min / 5min / 10min / 30min / 1h / +∞. 
Note: “0s” means on/off control; “+∞” means bi-level control, 100% 
on when motion detected, and remains at the stand-by dimming 
level when no presence is detected after hold-time.

13

13

Stand-by dimming level [ zone      ]

Press buttons in zone     to set the stand-by dimming level at 10% / 
20% / 30% / 50%.

14

14

6. Three Options for PIR Lens and Detection Patterns

Daylight harvest auto-configuration function

1. Press button “Shift”, the red LED is on for indication. 
2. Select a time period and the sensor will do light level measurement
    and determine/save the lowest light level (commission line) with 
   100% light on, so as to set the target lux level automatically. 
Note: 1. Make sure the light level measurement covers the night time.
         2. The fixture will go into sensor mode after the measurement,
              all sensor settings remain unchanged.

7

9

12

13

14

2

4

1

3

8

10

5

HRC-11

& A

4h

h

4

h

11

16

15

6

(End user can choose the suitable lens in real application for various requirements)

* For single person walking across, the detection range is reduced by 1/3.

PIR

HF

PIR detection: L x W x H:5 x 18 x 15m (max.)

HF detection: H x D:15 x 14m (max. )

15m

5m

14m

18m

PIR detection: H x D:15 x 18m (max.)
HF detection: H x D:15 x 14m (max.)

PIR

HF

PIR tangential movement 18m

HF walking across 14m

15m

PIR detection: L x W x H:18 x 5 x 15m (max.)

HF detection: H x D:15 x 14m (max. )

PIR

HF

15m

18m

14m

5m

Reviews: