2.2 Functions for sensor only (with sensor head)
Manual Override
DALI and swtich-Dim. can be connected at the same time, to enable manual override function for end-users to switch on/off or adjust the dimming
level by the push-switch. This feature makes the product more user-friendly, and could provide more options for some extra-ordinary demands.
Short push (<0.4s): on/off control.
Long push (>0.9s): dim up/down the dimming level.
If customers do not want to have this manual override function, just leave the “switch” terminal alone, and not connected to any wire.
This manual override is only valid before the next DALI command, meaning the latest action, either from DALI, switch-Dim, stays in control.
Permanent Memory
This driver has built-in permanent memory against power failure, which means the light always starts up at the previous level when it was switched off
last time.
SECTION 3 REMOTE CONTROL
Daylight Monitoring Function
Hytronik specially designed this function in software for deep energy-saving purpose. A built-in daylight sensor is designed to provide “smart photocell”
IXQFWLRQ7KLVIXQFWLRQFDQRQO\EHDFWLYDWHGZKHQVWDQGE\SHULRGLVVHWWR³´,QWKLVPRGHWKHODPSZLOODXWRPDWLFDOO\LOOXPLQDWHDWWKHGLPOHYHO
setting when the natural light goes below the threshold setting. The fixture will also switch off as the natural light returns.
Permanent ON/OFF [ ]
1. Press button , to select permanent ON or permanent OFF mode.
2. Press button to resume automatic operation. (Please refer to explanation below)
3. The mode will change to AUTO Mode after power failure.
Auto Mode [ ]
Press button to in initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.
1
2
2 3 4
button
1
button
2
5
9
4
11
12
Stand-by dimming level
Detection range
ON/
OFF
Auto Mode
Reset
Power
80%
Test
2s
10%
20%
30s
1min
100%
30min
10min
5min
0s
10s
1min
30%
SC1
SC2
SC3
Scene mode
10min
50%
10%
30min
Hold-time
Stand-by period
5min
Lux
Disable
2Lux
10Lux
50Lux
Daylight Sensor
SC4
Power
100%
+
-
Dim
M/A
3
1
2
7
8
6
10
13
14
15
HRC-05
Note: the buzzer beeps one time when RC
receives signal successfully
RESET [ ]
Press button , all settings go back to default settings:
Test 2s function [ ]
1.Press button ,the sensor goes into test mode (hold time2s). N.B. the stand-by period and daylight sensor settings are disabled in test mode.
2.Press button to exit from this mode, and the sensor settings are changed accordingly.
3
button
3
8
3 4 11
button
8
Detection range Hold time Stand-by period Stand-by dimming level Daylight sensor
100% 5min 10min 10% disable
This sensor reserves the access of manual override function for end-user to switch on/off, or adjust the brightness by push-switch, which makes the
product more user-friendly and offers more options to fit for some extra-ordinary demands:
* Short push (<1s): on/off function;
2QĺRIIWKHOLJKWWXUQVRIILPPHGLDWHO\DQGFDQQRWEHOLJKWHQIRUDFHUWDLQWLPHHTXDOVWRKROGWLPHSUHVHWHYHQPRYHPHQWLVGHWHFWHG
After this period, the sensor goes to sensor mode.
2IIĺRQWKHOLJKWWXUQVRQDQGJRHVWRVHQVRUPRGHQRPDWWHULIDPELHQW/X[OHYHOH[FHHGVWKHGD\OLJKWWKUHVKROGRUQRW
* Long push (>1s): dim up/down the hold-time brightness between 10% and 100%.
Note: if end-user do not want this manual override function, just leave the “push” terminal alone and don’t connect it to any wire.