background image

2.2 Functions for sensor only (with sensor head) 

Manual Override

DALI and swtich-Dim. can be connected at the same time, to enable manual override function for end-users to switch on/off or adjust the dimming 
level by the push-switch. This feature makes the product more user-friendly, and could provide more options for some extra-ordinary demands.

Short push (<0.4s): on/off control.     
Long push (>0.9s): dim up/down the dimming level.
If customers do not want to have this manual override function, just leave the “switch” terminal alone, and not connected to any wire.
This manual override is only valid before the next DALI command, meaning the latest action, either from DALI, switch-Dim, stays in control.

Permanent Memory

This driver has built-in permanent memory against power failure, which means the light always starts up at the previous level when it was switched off 
last time.

SECTION 3 REMOTE CONTROL

Daylight Monitoring Function

Hytronik specially designed this function in software for deep energy-saving purpose. A built-in daylight sensor is designed to provide “smart photocell” 

IXQFWLRQ7KLVIXQFWLRQFDQRQO\EHDFWLYDWHGZKHQVWDQGE\SHULRGLVVHWWR³’´,QWKLVPRGHWKHODPSZLOODXWRPDWLFDOO\LOOXPLQDWHDWWKHGLPOHYHO

setting when the natural light goes below the threshold setting. The fixture will also switch off as the natural light returns. 

Permanent ON/OFF [                ]

1. Press button    , to select permanent ON or permanent OFF mode.
2. Press button              to resume automatic operation. (Please refer to explanation below)
3. The mode will change to AUTO Mode after power failure.

Auto Mode [                ]

Press button     to in initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.

1

2

2 3 4

button

1  

button

2  

5

9

4

11

12

Stand-by dimming level

Detection range

ON/
OFF

Auto Mode

Reset

Power

80%

Test

2s

10%

20%

30s

1min

100%

30min

10min

5min

0s

10s

1min

30%

SC1

SC2

SC3

Scene mode

10min

50%

10%

30min

Hold-time

Stand-by period

5min

Lux

Disable

2Lux

10Lux

50Lux

Daylight Sensor

SC4

Power

100%

+

-

Dim

M/A

3

1

2

7

8

6

10

13

14

15

HRC-05

Note: the buzzer beeps one time when RC
          receives signal successfully

RESET [                ]

Press button    , all settings go back to default settings:

Test 2s function [                ]

1.Press button    ,the sensor goes into test mode (hold time2s). N.B. the stand-by period and daylight sensor settings are disabled in test mode.
2.Press button             to exit from this mode, and the sensor settings are changed accordingly.

3

button

3  

8

3 4 11

button

8  

Detection range                   Hold time                 Stand-by period                Stand-by dimming level               Daylight sensor

100%                               5min                           10min                                  10%                                     disable

This sensor reserves the access of manual override function for end-user to switch on/off, or adjust the brightness by push-switch, which makes the 
product more user-friendly and offers more options to fit for some extra-ordinary demands:
* Short push (<1s): on/off function;   

2QĺRIIWKHOLJKWWXUQVRIILPPHGLDWHO\DQGFDQQRWEHOLJKWHQIRUDFHUWDLQWLPHHTXDOVWRKROGWLPHSUHVHWHYHQPRYHPHQWLVGHWHFWHG

                   After this period, the sensor goes to sensor mode.

2IIĺRQWKHOLJKWWXUQVRQDQGJRHVWRVHQVRUPRGHQRPDWWHULIDPELHQW/X[OHYHOH[FHHGVWKHGD\OLJKWWKUHVKROGRUQRW

* Long push (>1s): dim up/down the hold-time brightness between 10% and 100%. 
Note: if end-user do not want this manual override function, just leave the “push” terminal alone and don’t connect it to any wire.

Manual Override 