![Hytronik HEC7430 Instruction Manual Download Page 2](http://html1.mh-extra.com/html/hytronik/hec7430/hec7430_instruction-manual_2194896002.webp)
Section 2 Settings
Detection range can be tuned by selecting the combination on the DIP switches to fit precisely for each specific application.
Detection range
I – 100%
II – 75%
III – 50%
IV – Sensor OFF
50 %
75%
100 %
Sensor OFF
2
1
I
II
III
IV
This setting determines the time period the lamp will remain at 100% upon detection.
Note: the timer is reset upon each motion detection.
Hold-time
I – 5s
II – 30s
III – 3min
IV – 10min
5s
30s
3min
10min
4
3
I
II
III
IV
The daylight threshold can be set on the DIP switches suit to the particular application.
1RWH³V´PHDQVRQRIIFRQWURO³´PHDQVELOHYHOGLPPLQJFRQWUROIL[WXUHQHYHUVZLWFKRIILHWKHOLJKWUHPDLQVDWWKH
stand-by dimming level until motion is detected.)
Daylight sensor
I – Disable
II – 50Lux
III – 10Lux
IV – 5Lux
This is the time period setting to keep at the low light output level before it is completely switched off in the long absence of
people.
Stand-by period (corridor function)
I – 0s
II – 10s
III – 30min
,9±
This is the dimmed low light output level setting after the hold-time has expired.
Stand-by dimming level
I – 10%
II – 30%
6
5
50Lux
10Lux
5 Lux
Disabl
e
I
II
III
IV
V
30%
10%
9
I
II
0s
10s
30min
8
7
I
II
III
IV
+
Section 3 Sensor Antenna & RC Settings
Work with remote control
HRC-05.
Super-compact sensor
antenna, with optional
FDEOHHQWU\VLGHHQWU\
and back entry)
Model SAM5
Cable side entry
Infrared remote receiver
Daylight sensor
40.4
11.2
6.8
8.8
35.9
2.5
13
25.2
30.7
Cable back entry