Hytronik HC403VRC-KD Installation And Instruction Manual Download Page 3

4. Section Functions

HC403VRC-KD-20170329-A1

Hytronik Industrial Ltd.  |  www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai'gang road south, 
Bo'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020   Fax: 86-752-2777877  

Note: “Os” means on/off control;“+

”means bi-level dimming control, fixture never switches off when 

          daylight sensor is disabled.

This is the dimmed low light output level setting after the hold-time has expired.

Stand-by dimming level

I –  10%
II –  20%
III – 30%
IV – 50%

30%

20%

10%

50%

2

1

I

II

III

IV

The light will not come on

The lamp is always on

The lamp is on without any 

identifiable movement

The lamp will not work 
despite movement                                   

Incorrect light-control setting 
selected
Faulty lamp
No power supply

Continuous movement in the 
detection zone 

The sensor is not mounted for 
reliably detecting movement

Movement occurred, but not 
identified by the sensor (Movem
ent behind wall, movement of 
small object in immediate lamp 
vicinity etc.)

Rapid movements are being supp
ressed to minimize malfunctioning 
or the detection radius is too small.

5. Section Trouble Shooting

Cause                                Remedy    

Malfunction Cause 

Remedy 

Adjust daylight threshold 
setting
Replace lamp
Check power to sensor

Check detection area 
setting

Securely mount enclosure

1. Reduce sensitivity.

2. Check the movement 

    behind walls to avoid 

    facilities such as water 

    pipe, fan, which may 

    mis-trigger the sensor.

Check detection area  
settingng

I – 0s
II – 10s
III – 1min
IV – 5min
V –  10min
VI – 30min
VII – 1h
VIII – +∞                                 

10s

1min

5min

10min

30min

1h

3

2

1

+

0s

I

II

III

IV

V

VI

VII

VIII

This is the time period setting to keep at the low light output level before it is completely switched off in 

the long absence of people.

Stand-by period (corridor function)

Double L N terminal makes it easy for wire loop-in and loop-out, and saves the cost of terminal block 
and assembly time.  

4.3 Loop-in and Loop-out Terminal

4.1 Zero-cross Relay Operation

Designed in the software, the sensor switches on/off the load right at the zero-cross point, to ensure 
the in-rush current is minimised, enabling the maximum life-time of the relay.

4.2 Daylight Monitoring Function

Hytronik specially designed this function in software for deep energy-saving purpose. A built-in 
daylight sensor is designed to provide “smart photocell” function. This function can only be activated 
when stand-by period is set to “+∞”. In this mode the lamp will automatically illuminate at the dim 
level setting when the natural light goes below the threshold setting. The fixture will also switch off 
as the natural light returns. 