1. Technical Specifications
Product Type Microwave Motion Sensor
Operating Voltage 120-277VAC 50Hz/60Hz
Hf System:
5.8GHz Cw Radar
Rated Load: 400w / 3.6a / 120v
(capacitive load) 800w / 3.6a / 230v
1000w / 3.6a / 277v
Detection Angle: 30°~150°
Power Consumption: <1w
Detection Range (dxh): Max. 12 X 6m(sam5)
Max. 12 X 6m(sam6)
Time Setting: 5s, 30s~30min.
Daylight Sensor: 2~50lux; Disable
Stand-by Period: 0s, 10s ~ 1h,
+∞
Stand-by dimming level 10% ~ 50%
Mounting:
Indoors,ceiling & walling mounted
Working Temp.:
-20
o
C ~ +60
o
C
HC403VRC-KD-20170329-A1
Important
Please read these instructions carefully prior to installation and retain this leaflet in a known
and safe place for future reference.
SAM5
SAM6
HC403VRC-KD HRC-05
Adjustable
detection area
Buzzer
Hold-time
Stand-by period
Stand-by
dimming level
Sensor antenna interface
Daylight threshold
1-10V
+
Stand-by dimming level
Detection range
ON/
OFF
Auto Mode
Reset
Power
80%
Test
2s
10%
20%
30s
1min
100%
30min
10min
5min
0s
10s
1min
30%
SC1
SC2
SC3
Scene mode
10min
50%
10%
30min
Hold-time
Stand-by period
5min
Lux
Disable
2Lux
10Lux
50Lux
Daylight Sensor
SC4
Power
100%
+
-
Dim
M/A
The sensor is an active motion detector; it emits a high-frequency electro-magnetic wave at 5.8GHz and receives
its echo.The sensor detects the change in echo from movement in its detection zone. A microprocessor then
triggers the switch light ON command. Detection is possible through doors, panes of glass and thin walls.
Note: the high-frequency output of this sensor is <0.2mW; approximately just 0.2‰ of the transmission power of
a mobile telephone.
2.1 Ensure that the electricity supply is switched off before installing or
servicing this product.
2.2 Wiring diagram
LED Driver
LED
Installation and Instruction Manual
HF MOTION SENSOR DETACHED VERSION HC403VRC-KD
30.7 35.9 40.4
16.2
25.2
6
2.5
11.2
1.8
6.8
φ
5
22.5
φ
4
Drill hole 9mm x 3mm
Drill hole 9mm x 3mm
Drill hole for cable entry is 10mm x 10mm in
square shape or
φ
12mm in round shape
option 1
option 2
Slots for T8 tube
50.2
26.5
45.2
32.2
2.5
33.5
Slots for T5 tube
26.5
50.2
15
9
2
12
33.5
Drill hole 9mm x 3mm
Drill hole 9mm x 3mm
Drill hole for cable entry is 10mm x 10mm in
square shape or
φ
12mm in round shape
22.5
2.5
13
φ
4