Scene program - 

1-key commissioning

Detection range

Press buttons in zone “Detection range” to set detection range at 100% / 75% / 50% / 10%.

Press buttons in zone “ Daylight threshold” to set daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / 500Lux / Disable.

Note:  To set daylight sensor at 100Lux / 300Lux / 500Lux, press “Shift” button first.

Daylight threshold

1. Press button “Start” to program.
2. Select the buttons in “Detection range”, “Daylight threshold”, “Hold-time”, “Stand-by time”, “Stand-by dimming level” to set all 
parameters.
3. Press button “Memory” to save all the settings programmed in the remote control.
4. Press button “Apply” to set the settings to each sensor unit(s).     
    

For example, to set detection range 100%, daylight threshold Disable, hold-time 5min, stand-by time +∞, stand-by dimming level 30%, the steps should be:  

    Press button “Start”, button ”100%”, “Disable”, “Shift”, “5min”, “Shift”, “+∞”, “30%”, “Memory”. By pointing to the sensor unit(s) and pressing “Apply”, all 
    settings are passed on the sensor(s).

1. Press button “Shift”, the red LED starts to flash. 
2. Press button “Ambient”, the surrounding lux level is sampled and set as the new daylight threshold.

Ambient daylight threshold

Hold-time

Press buttons in zone “hold-time” to set the hold-time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.

Note: 1. To set hold-time at 30s / 5min / 15min / 30min, press “Shift” button first.
          2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode.

*To exit from Test mode, press button “RESET” or any button in “Hold-time”.    

Stand-by dimming level

Stand-by time (corridor function)

Press buttons in zone “stand-by time” to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞. 

Note: “0s” means on/off control; “+∞” means bi-level control, the fixture is 100% on when there is motion detected, and remains at the stand-by dimming level 
         when no presence after motion hold-time.

Press the button in zone “stand-by dimming level” to set the stand-by dimming level at 10% / 20% / 30% / 50%.

Dual tech & RF mode

 1. Press buttons in this zone to select sensor technology.
     HF+PIR: the light is on when both HF and PIR sensors are activated.
     HF/PIR: the light is on when HF or PIR sensors are activated.
 2. Learn / Erase, Transmit, RX100% and RX STBY% are disabled.

Auto-configuration function

All buttons in this zone are disabled.

Note: the function of 24h/12h/4h/30s are disabled.

Summary of Contents for Dual Sense HIM31

Page 1: ...r Data Operation temperature Ta 20 O C 50 O C Environment IP65 IP rating 30s Warming up Technical Data Mechanical Structures and Installations For more details please refer to user manual TM HIM31 Mod...

Page 2: ...ion fans water pipe elevators etc in industrial application no penetration confined detection area sensitive to tangential movement resilient to motion object which has no heat radiation can be false...

Page 3: ...tch Programing Functions and Features HF Microwave only PIR PIR mode only HF PIR both PIR and microwave mode to decrease the detection capability and detection area Only when both detections are activ...

Page 4: ...ttons to select light output at 80 at initial 10 000 hours or 100 Note Sensor off and Twilight functions are disabled Settings Remote Control HRC 11 Press button RESET all settings go back to rotary s...

Page 5: ...Ambient the surrounding lux level is sampled and set as the new daylight threshold Ambient daylight threshold Hold time Press buttons in zone hold time to set the hold time at 2s 30s 1min 5min 10min...

Page 6: ...ction H x D 15 x 14m max PIR HF 15m 18m 14m 5m PIR HF PIR detection L x W x H 5 x 18 x 15m max HF detection H x D 15 x 14m max 15m 5m 14m 18m Wiring Diagram Detection Pattern End user can choose the s...

Page 7: ...m download knowledge Microwave Sensors Precautions for Product Installation and Operation 2 Regarding precautions for PIR sensor installation and operation please kindly refer to www hytronik com down...

Reviews: