Hytronik DUAL sense HIM17 Quick Start Manual Download Page 5

Subject to change without notice.

Edition: 26 Feb. 2020      Ver. A0      Page 5/6

PIR

HF

PIR tangential movement 10m

HF walking across 8m

3m

PIR

HF

B

PIR

HF

A

3m

4m

PIR tangential movement 10m

HF walking across 8m

3m

PIR tangential movement 10m

HF walking across 8m

Detection Pattern

Press buttons in zone “ Daylight threshold” to set daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / 500Lux / Disable.

Note:  To set daylight sensor at 100Lux / 300Lux / 500Lux, press “Shift” button first.

Daylight threshold

1. Press button “Shift”, the red LED starts to flash. 
2. Press button “Ambient”, the surrounding lux level is sampled and set as the new daylight threshold.

Ambient daylight threshold

Hold-time

Press buttons in zone “hold-time” to set the hold-time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.

Note: 1. To set hold-time at 30s / 5min / 15min / 30min, press “Shift” button first.
          2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode.

*To exit from Test mode, press button “RESET” or any button in “Hold-time”.    

Stand-by time (corridor function)

Press buttons in zone “stand-by time” to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞. 

Note: “0s” means on/off control; “+∞” means bi-level control, the fixture is 100% on when there is motion detected, and remains at the stand-by dimming level 
         when no presence after motion hold-time.

Stand-by dimming level

Press the button in zone “stand-by dimming level” to set the stand-by dimming level at 10% / 20% / 30% / 50%.

Dual tech & RF mode

 1. Press buttons in this zone to select sensor technology.
     HF+PIR: the light is on when both HF and PIR sensors are activated.
     HF/PIR: the light is on when HF or PIR sensors are activated.
 2. Learn / Erase, Transmit, RX100% and RX STBY% are disabled.

PUSH

L’

N
N

L

L

N

L

Trailing edge 

dimmable driver

L

N

Trailing edge 

dimmable driver

HIM17

N

Wiring Diagram

Auto-configuration function

All buttons in this zone are disabled.

Reviews: