Subject to change without notice.
Edition: 26 Feb. 2020 Ver. A0 Page 3/6
Tri-level Control (Corridor Function)
2
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice
before switch-off. The sensor offers 3 levels of light: 100%-->dimmed light (natural light is insufficient) -->off; and 2 periods of
selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
Manual Override
3
* Short Push (<1s): on/off function;
On
→
Off: the light turns off immediately and cannot be triggered ON by motion until the expiration of pre-set hold-time. After this
period, the sensor goes back to normal sensor mode.
Off
→
On: the light turns on and goes to sensor mode, no matter if ambient Lux level exceeds the daylight threshold or not.
* Long Push (>1s): adjust the hold-time brightness level between10% and 100%.
Note: if end-user do not want this manual override function, just leave the “push” terminal unconnected to any wire.
With the help of push-switch, this sensor can be over-ridden by the end-user to manually switch on/off the light, or adjust the
brightness by push-switch, which makes the product more user-friendly and offers more options to fit some extra-ordinary demands:
Semi-auto Mode (Absence Detection)
4
It is easy to forget to switch off the light, in office, corridor, even at home. And in many other cases, people do not want to have a
sensor to switch on the light automatically, for example, when people just quickly pass-by, there is no need to have the light on. The
solution is to apply this “absence detector”: motion sensor is employed, but only activated on the manual press of the push-switch, the
light keeps being ON in the presence, and dims down in the absence, then switches off in the long absence.
Note: end-user can choose either function or function for application. Default function is manual override.
3
4
Double L N terminal makes it easy for wire loop-in and loop-out, and saves the cost of terminal block and assembly time.
Loop-in and Loop-out Terminal
5
A rotary switch is built inside the sensor for scene
selection / fast programming. Total 16 channels
are available:
Rotary switch preset
Rotary Switch Preset
Note: settings can also be changed by remote control
HRC-11. The last action controls.
0
5s
100%
Disable
1
1min
100%
2Lux
2
5min
100%
10Lux
3
5min
100%
30Lux
4
5min
100%
10Lux
5
5min
100%
30Lux
6
5min
100%
Disable
7
10min
100%
2Lux
8
10min
100%
10Lux
9
10min
100%
30Lux
A
10min
100%
Disable
B
10min
75%
30Lux
C
10min
50%
10Lux
D
30min
100%
50Lux
E
30min
100%
Disable
F
5s
100%
10%
10%
10%
10%
Disable
10%
30%
10%
10%
10%
30%
10%
10%
10%
30%
10%
2Lux
10s
5min
10min
30min
0s
+∞
+∞
10min
30min
+∞
+∞
+∞
+∞
+∞
+∞
10s
Detection
range
Channel
Hold-time
Stand-by
time
Stand-by
dim level
Daylight
sensor