S709/8
8. The lower line will show the following
in a looping sequence:
1 DECIMAL PLACE
- One decimal
place on display
2 DECIMAL PLACE
- Two decimal
places on display
Press calibration button once when
desired option is displayed.
9. The lower line will show the following
in a looping sequence:
REED RELAY 10
- Ten pulse per litre
reed relay output.
OPTO OUTPUT 10
- Ten pulse per
litre opto-isolated output.
OPTO OUTPUT 100
- One hundred
pulse per litre opto-isolated output.
Press calibration button once when
desired option is displayed.
10. The lower line will show the following
in a looping sequence:
TANK SW UNUSED
– No “tank
empty” switch connected.
TANK SW IS TA.F
– “Tank empty”
switch connected is Hytek TA.F type.
TANK SW NOT TA.F
– “Tank empty”
switch
connected
is
standard
“normally closed” float switch.
11. The lower line will show the following
in a looping sequence:
LEAK SW UNUSED
– No “pump leak”
switch connected.
LEAK SW IS TA.F
– “pump leak”
switch connected is Hytek TA.F type.
LEAK SW NOT TA.F
– “pump leak”
switch
connected
is
standard
“normally open” float switch.
00000.0
CALIB
1 DECIMAL PLACE
00000.0
CALIB
OPTO OUTPUT 10
00000.0
CALIB
TANK SW IS TA.F
00000.0
CALIB
LEAK SW IS TA.F