13 User Manual
Information on grounding components:
Note: PE cable requirements
Object
Description
1
Housing
2
M6 terminal lug with protective conductor
3
M6
×12 pan head screw
Diameter
Cross-section
备注
16<S
≤
35mm
2
16mm
2
Only suitable when the material of PE
cable is aligned with other AC phase
cables. In case the materials are
different, please ensure the resistance is
equivalent to the figure mentioned in
the table.
S>35mm
2
S/2
Please install the secondary PE before connect any other cables.
Secondary PE cannot replace the connection of PE terminal in AC wiring. Both PE and
secondary PE should be properly installed.
Hypontech will not take account for any consequences caused by violating the
requirement.