Page 6
1.4 Intended Use
The kit serves for steam production based on
tap water or partially softened water.
Only use supply water featuring a con-
ductivity of 125 to 1250 µS/cm.
D1: Lower threshold
C1: Range of reduced conductivity
(adjustment required)
A: Normal Tap water
B: Range of increased conductivity
C2: Range of high conductivity
(adjustment required)
D2: Upper threshold
In the C1 and C2 ranges, adaptation of the
periodic blow-down frequency may be
required.
Proper usage also comprises the adherence
to the conditions specified by HygroMatik for:
•
installation
•
dismantling
•
reassembly
•
commissioning
•
operation
•
maintenance
•
disposal.
Only qualified and authorised personnel may
operate the unit. Persons transporting or
working on the unit must have read and
understood the corresponding parts of the
Operation and Maintenance Instructions and
especially the chapter 2. „Safety Notes“.
Additionally, operating personnel must be
informed of any possible dangers. You
should place a copy of the Operation and
Maintenance Instructions at the unit‘s opera-
tional location (or near the unit).
By construction, the kit is not qualified for
exterior application.
Risk of scalding!
Steam with a temperature of up to 100 °C is
produced.
Do not inhalate steam directly!
1.5 Possibility of certification
HygroMatik humidifiers are certified accord-
ing to the household appliance standard DIN
EN 60335-1 in accordance with the special
requirements for humidifiers DIN EN 60335-
2-98 and comply with the requirements of the
EC Low Voltage Directive 2014/35/EU con-
tained therein.
It has been shown by the legislator through a
risk analysis in accordance with the Machin-
ery Directive that the risks are mainly of elec-
trical origin and that all essential safety
requirements of the Machinery Directive
together with the main objectives of the Low
Voltage Directive are covered by the EN
60335-2-98 standard.
HygroMatik humidifier installation kits corre-
spond in their construction to the certified
humidifiers. Due to the lack of enclosure, wir-
ing and only optional control, they are incom-
plete in the broader sense, but not an
incomplete machine in accordance with the
Machinery Directive 2006/42 / EC.