Page 38
»
Put the cylinder halves together and
reconnect them with the flange
clamps.
Risk of functional disruption!
We generally advise against using limescale
removers or other cleaners. If these are nev-
ertheless used to clean the cylinder and the
electrodes, rinse the parts cleaned with them
thoroughly before putting the unit back into
operation. The cleaners may impair the con-
ductivity of the cylinder water.
9.3.3 Cleaning the connecting hoses,
base connections, fine filter
and drain pump
»
Check the connection hoses for con-
dition and free passage.
»
Check all connections of the cylinder
base for free passage.
»
Clean the hoses and connections if
necessary.
»
Remove the fine filter on the water
connection side from the solenoid
valve and clean it under running
water.
»
Clean the drain pump as described
in the section of the same name..
9.3.4 Cleaning the vent hole on the
pipe elbow
The pipe elbow is only accessible when the
steam cylinder is removed.
»
Remove the pipe elbow from the
back wall of the housing by
unscrewing the fixing screw of the
pipe elbow.
»
Check the small opening on the top
of the pipe elbow for dirt.
»
Remove any dirt, e.g. with a small
screwdriver.
»
Reattach the pipe elbow to the back
wall of the housing with the screw.
The vent hole should be checked for free cir-
culation during every maintenance. A
blocked vent hole has a negative effect on
the drainage process (see also chapter
"Trouble shooting" in the manual of the con-
trol).
NOTICE
Please note