Risk of material damage!
Excessive tightening will destroy the solenoid fitting thread.
Do not overtighten the cap nut.
»
Screw the other hose end cap nut with its inner seal on
a customer-provided water tap (cup nut internal thread
is ¾“).
6.3 Water discharge
Risk of scalding!
During blow down up to .3 l/sec (.08 gal./sec) are being drained
with a temperature of about 95 °C/203 °F.
Wastewater must drain freely and pressureless!
Avoid contact in order not to burn skin.
With the optional wastewater cooling system
HyCool
, HygroMa-
tik offers an option for limiting the wastewater temperature of the
steam humidifier in order to protect thermosensitive wastewater
pipe lines. By blending with cold water during the blow-down and
rinse process, it is ensured that the wastewater always has a
temperature below 60°C/140°F.
Steam humidifier and wastewater discharge must be on the
same pressure level.
Guidelines for water discharge composition
•
Use of flexible drain hose is advisable
•
Do not buckle the drain hose
•
For discharge line and drain pipe implementation,
select temperature-resistant materials allowing up to
95°C/203°F
•
Take care that ascending vapor does not condensate
on humidifier cabinet
How to proceed
»
Run a 1 1/4 " drain hose of 10 to 40 inch length into a
pressure-free outlet (DIN EN 1717 is a good design
reference for adequate drain composition).
»
Slide other drain hose end over cabinet drain connec-
tion stub on the housing bottom side and secure with a
clamp.
Please note