5.2.2 Fan Unit Cover
Covers for humidifier types HY05 and HY30 are optionally avail-
able to protect the steam and condensate hoses between the
steam humidifier and the fan unit. The vertical distance between
the humidifier and the fan unit is determined by the height of the
cover (see table of dimensions, H).
»
Drill two holes in the housing as specified in the follo-
wing diagram.
»
Install the steam humidifier and fan unit on the wall at a
distance given by the front cover (measure H).
»
Secure the steam hose between the humidifier and fan
unit with hose clamps.
»
Also using a hose clamp, attach the condensate hose
to the fan unit.
»
Run condensate hose along the rear of the unit to the
water discharge (see also chapter "Water Discharge").
»
Lay the condensate hose with a 200 mm loop directly
over the drain. The loop acts as a vapor barrier.
Condensate cannot be fed back into the steam cylinder.
»
Slide cover between humidifier and fan unit.
»
Fasten cover with the two screws supplied. Screw from
the steam panel outwards.
Unit type H [in/mm] I [in/mm] J [in/mm] K [in/mm]
HY05-HY08
6.9/175
3.1/80
14.7/373 10.5/266,5
HY13-HY23
11/280
4.1/105 16.6/422 12.2/310
HY30
11/280
4.1/105 17.8/452 13.4/340
Please note