WARNINGS AND LIMITATIONS

 

 

Our devices use high quality electronic components and plastic materials that are highly 

resistant to environmental deterioration.  

However, after 10 years of continuous operation, it is advisable to replace the devices 

in order to minimize the risk of reduced performance caused by external factors.  

Ensure that this device is only used with compatible control panels.  

Detection  systems  must  be  checked,  serviced  and  maintained  on  a  regular  basis  to 

confirm correct operation.  

Smoke sensors may respond differently to various kinds of smoke particles, thus appli-

cation advice should be sought for special risks.  

Sensors  cannot  respond  correctly  if  barriers  exist  between  them  and  the  fire  location 

and may be affected  by special environmental conditions.  

Refer to and follow national codes of practice and other internationally recognized fire 

engineering standards.  

Appropriate risk assessment should be carried out initially to determine correct design 

criteria and updated periodically. 

 

WARRANTY

 

 

All  devices  are  supplied  with  the  benefit  of  a  limited  3  year  warranty  relating  to  faulty 

materials or manufacturing defects, effective from the production date indicated on each 

product.  

This warranty is invalidated by mechanical or electrical damage caused in the field by 

incorrect handling or usage.  

Product must be returned via your authorized supplier for repair or replacement togeth-

er with full information on any problem identified.  

Full details on our warranty and product’s returns policy can be obtained upon request.

 

Sterling Safety Systems  

Unit B12a, Holly Farm Business Park, Honiley, Warwickshire, 

CV81NP - UK  

 

19 

 

HF-20-002CPR 

HFI-EBS-06 

HFI-ABS-06 

 

 

HF-20-003CPR 

HFI-EBSB-23W-06   

HFI-EBSB-23R-06 

HFI-ABSB-23W-06 

HFI-ABSB-23R-06 

EN 54-3:2001+A1:2002+A2:2006  

Fire alarm devices - Sounders 

 

HFI-EBS-06 

HFI-EBSB-23W-06 

HFI-EBSB-23R-06 

HFI-ABS-06 

HFI-ABSB-23W-06 

HFI-ABSB-23R-06 

 

EN 54-23:2010 

Fire alarm devices - Visual Alarm Devices 

 

HFI-EBSB-23W-06 

HFI-EBSB-23R-06 

HFI-ABSB-23W-06 

HFI-ABSB-23R-06 

 

Type A - Intended for indoor use only 

For use in compatible fire detection and alarm systems 

Other technical data: see TDS-BSXXX held by the manufac-

turer 

 

Category rating:  

C 3 - 15 & O 4.5 - 15.2 

HFI-EBSB-23W-06

 & 

HFI-ABSB-23W-06

 (high power) 

 

C 3 - 10 

HFI-EBSB-23R-06

 & 

HFI-ABSB-23R-06

 (high power) 

 

C 3 - 9.2 

HFI-EBSB-23W-06

 & 

HFI-ABSB-23W-06

 (low power) 

 

O 1.7 - 6.0 

HFI-EBSB-23R-06

 & 

HFI-ABSB-23R-06

 (low power) 

 

Duration of operation: Pass 

Provision for external conductors: Pass 

Flammability of materials: Pass 

Enclosure protection: Pass 

Access: Pass 

Manufacturer's adjustments: Pass 

On-site adjustment of behaviour: Pass 

Requirements for software controlled devices: Pass 

Coverage volume: Pass 

Variation of light output: Pass 

Minimum and maximum light intensity: Pass 

Light colour: White (

HFI-EBSB-23W-06

 & 

HFI-ABSB-23W-06

Light colour: Red (

HFI-EBSB-23R-06

 & 

HFI-ABSB-23R-06

Light temporal pattern / frequency of flashing: N/A / 0.5 Hz 

Marking and data: Pass 

Synchronization: Pass 

Durability: Pass 

Temperature resistance: Pass 

Humidity resistance: Pass 

Shock and vibration resistance: Pass 

Corrosion resistance: Pass 

Electrical stability: Pass 

[email protected] 

L20-HFIAEB6-1400 (vA.2)  

Reviews: