background image

Step 3  

Wiring  

Select the wiring diagram 

through 

below that corresponds to the 

low water cut-off installed on the boiler.

Consult boiler manufacturer’s instructions for proper burner terminal connections.

McDonnell & Miller 

Note: 

If there is no jumper installed on the low water cut-off

between 1 and P1, see 

ALTERNATE WIRING

box.

Note: 

If there is no jumper installed on the low water cut-off

between H and C, see 

ALTERNATE WIRING

box.

Note: 

If there is no jumper installed on the low water cut-off

between H and P1, see 

ALTERNATE WIRING

box.

Note: 

If there is no jumper installed on the low water cut-off

between 1 and 3, see 

ALTERNATE WIRING

box.

Hydrolevel

Safgard Model 450 / CycleGard CG450

STANDARD WIRING

PS-800 Series

– Newer Models

STANDARD WIRING

PS-800 Series

– Older Models

STANDARD WIRING

Safgard Model OEM-170TD

STANDARD WIRING

IMPORTANT

To prevent over-feed-

ing and possible

flooding, when used

with the OEM-170TD,

the VXT should be set

with a Feed Delay of

10 minutes and a

Feed Amount of 1 to 5

gallons (see step 5). 

DO NOT USE LWCO

SETTING.

Float Style Control

ALTERNATE WIRING

Safgard & CycleGard Models: 

If there is no jumper installed between terminals 1 and P1 on the low cut-off
(between H and P1 on Model OEM-170TD), then the cut-off is powered by a
separate power source from the burner circuit and the following wiring must
be used:

Connect a wire from the FEED terminal on the feeder to the A

terminal on the cut-off. 

Connect a wire from terminal H on the feeder to

the  burner  circuit  hot. 

Connect  a  wire  from  terminal  N  on  the  feeder  to

burner circuit neutral.

ALTERNATE WIRING

PS-800 Series: 

If there is no jumper installed between terminals H and C on the low water
cut-off (terminals 1 and 3 on older models), then the cut-off is powered by a
separate power source from the burner circuit and the following wiring must
be used: 

Connect a wire from the FEED terminal on the feeder to the W

(4 on older models) terminal on the cut-off. 

Connect a wire from terminal

H on the feeder to the burner circuit hot. 

Connect a wire from terminal N

on the feeder to burner circuit neutral.

Using a separate power source for the feeder

Honeywell

Model RW-700 Guard Ring

Using the burner circuit to power the feeder

Reviews: