Hydrolevel Company Safgard 1150 Instructions Download Page 3

OPERATIONAL TEST PROCEDURE

IMPORTANT: Do not run boiler unattended until the following procedure is completed

1.

Before raising the water level above the Model 1150, turn on power to the boiler and set the thermostat to call for heat. Both

the green “POWER” LED and amber “LOW WATER” LED should illuminate. The burner should not fire. IMPORTANT: If the

burner fires with no water at the probe, immediately shut down power to the boiler and refer to the Trouble Shooting instruc-

tions below.

2.

Proceed to fill the boiler with water. When water reaches the LWCO position, the burner should fire. If the burner does not

fire, refer to the Trouble Shooting instructions below.

3.

Turn off the power to the boiler and finish filling the system.

4.

Before leaving the job, power up the system and push the TEST button on the Model 1150 to simulate a low water condition.

The amber “LOW WATER” LED should illuminate and the burner should shut down.

MAINTENANCE

EVERY YEAR

Check control operation annually by pressing the TEST button. The amber “LOW WATER” LED should illu-

minate and the burner should shut down.

5 YEARS

Remove the low water cut-off every five years and clean all surfaces in contact with water.

TROUBLE SHOOTING

IF THE BURNER DOES NOT SHUT DOWN

(when water is below the probe or when the TEST button is pressed)

1.

Turn off boiler power immediately and re-check wiring.

2.

Turn off boiler power and drain system. Remove low water cut-off and check for adequate clearance – no metal should be in

contact with the controlʼs metal probe tip.

IF THE BURNER DOES NOT FIRE

1.

Make sure water has reached the level of the control.

2.

Check for proper ground. The 1150 grounds through the probe to the boiler shell or pipe tee. The control box mounting

screws ground the circuit board to the probe. Check to ensure that both mounting screws are tightened securely and that the

probe is not insulated from the boiler shell or tee with excessive use of Teflon tape or sealing compound.

3.

Check to ensure the controlʼs metal probe tip is not surrounded by an air pocket. Shut down power to the boiler and

slowly loosen, but do not remove, the control. Allow any air to escape. When water begins to seep past threads, retighten

the control.

4.

Re-check wiring and check for correct incoming voltage.

Model 1150 Instructions: Model 1150 Instructions  9/24/10  9:17 AM  Page 5

Summary of Contents for Safgard 1150

Page 1: ...or pipe Do not install in a location that could hold or trap water in the event of a low water condition Remove center extended nut Apply pipe sealing compound to probe threads and install in boiler or tee Tighten so that the two smaller extended nuts are horizontally aligned Mount the control box on the probe by aligning the keyhole slots with the two extended nuts Replace the center extended nut...

Page 2: ...20 VAC lead coming from the service switch Step Connect the second yellow wire CUT OFF from the Safgard 1150 to the L1 boiler connection Connect the black wire H from the Safgard 1150 to the hot 120 VAC lead coming from the service switch Connect the white wire N to the neutral 120 VAC lead Locate and break into the burner circuit Connect the yel low wires CUT OFF from the Safgard 1150 in series w...

Page 3: ...er should shut down 5 YEARS Remove the low water cut off every five years and clean all surfaces in contact with water TROUBLE SHOOTING IF THE BURNER DOES NOT SHUT DOWN when water is below the probe or when the TEST button is pressed 1 Turn off boiler power immediately and re check wiring 2 Turn off boiler power and drain system Remove low water cut off and check for adequate clearance no metal sh...

Page 4: ...y other loss or damage whether direct indirect incidental or consequential This war ranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other warranty or guarantee express or implied includ ing without limitation any warranty of MERCHANTABILITY or fitness for a particular purpose This warranty may not be assigned or transferred and any unauthorized transfer or assignment thereof shall be v...