When there is no call to fire the burner, the voltage

should be 0 volts between B1 and B2.

 

Make sure the burner is wired to B1.

YES

NO

Is the 

Low Limit Dial

Set to OFF?

Is there 

24 VAC between

B1 and B2?

NO

Is the

Thermostat 

(T-T) Calling 

for Heat?

YES

YES

Is the 

Domestic Water 

(I1-I2) Calling for

Heat?

NO

NO

Is the

Red LED

(LOW WATER)

On?

The Control is

Sensing

Low Water.

WARNING!

TURN OFF POWER TO BURNER IMMEDIATELY!

CAUTION – ALWAYS ALLOW A BOILER TO FULLY COOL

BEFORE ADDING WATER.

Recheck wiring. Make sure that burner is wired to

B1. Burner should never fire when red or yellow

LED is lit.

Is either

Yellow LED

On?

The Control has

Reached Target

or High Limit

Temperature.

The Control is

Operating 

Normally.

The Control is

Operating 

Normally.

The burner will continue to fire when there is a call

from the thermostat or external zone.

 

Check temperature display. When the Low Limit is

set, the HydroStat will fire the burner until the

temperature reaches the Low Limit Setting.

If there is no call for heat (from T-T, I1-I2 or Low

Limit), there should be 0 VAC between B1-B2. 

 

If there is voltage between B1-B2, the control

should be replaced.

Troubleshooting Flow Chart 2 – Burner Will Not Shut Down

YES

YES

NO

NO

8

Summary of Contents for Fuel Smart HydroStat 3200

Page 1: ...l boilers Low Water Cut Off Provides protection against potentially dangerous low water conditions when installed with the Hydrolevel Electro Well see page 2 for details Boiler Reset Control Utilizes...

Page 2: ...osen Fig 3 IMPORTANT Make sure that the immersion well or Electro Well is installed in the boiler manufacturer s designated temperature limit control tapping N NO OT TE E If installing an Electro Well...

Page 3: ...he vent damper plug is disconnected ZONE VALVE WIRING IMPORTANT Use a separate transformer to power zone valves Connecting zone valves to Z TV may overload the HydroStat and cause a lock out condition...

Page 4: ...P Differentials are automatic and will vary based on control settings and boiler temperature Thermal Targeting technology analyzes thermostat activity and continually evaluate how much heat the house...

Page 5: ...ed using the ECONOMY dial See How Thermal Targeting Works on page 4 for more information ECONOMY TARGET When the Economy feature is active the Fuel Smart HydroStat continually sets target temperatures...

Page 6: ...anticipator settings common on non digital thermostats 3 Check the Economy setting The Economy feature much like outdoor reset controls lowers average boiler temperature and can slow or in some cases...

Page 7: ...rol is Operating Properly Replace Control The burner will not fire until the boiler water has dropped to the high limit differential set point 10 below high limit setting Check that the high temperatu...

Page 8: ...ck wiring Make sure that burner is wired to B1 Burner should never fire when red or yellow LED is lit Is either Yellow LED On The Control has Reached Target or High Limit Temperature The Control is Op...

Page 9: ...riod of two years from the date of manufacture or one year from the date of installation whichever occurs first In the event of any claim under this warranty or otherwise with respect to our products...

Reviews: