8
3.5 ELECTRICAL
WARNING: This appliance must be earthed. It is suitable for a.c. supply only.
Disconnect the electrical supply before removing the terminal cover. Installation
must be in accordance with the current I.E.E. Wiring Regulations.
3.5.1 The unit is supplied fitted with a 0.75m 3 core 1mm
2
flexible cable. The
electricity supply should be fused 13 Amp and be via a double pole
isolating switch with a contact separation of at least 3mm in both poles.
Refer to the schematic wiring diagram Figure 05 below.
3.5.2 The wires are colour coded as follows:
Green and Yellow
EARTH
Brown
LIVE
(L)
Blue
NEUTRAL
(N)
BN
BL
BN
BL
BK
NEON
ELEMENT
COMBINED THERMOSTAT
& OVER TEMPERATURE
CUT-OUT
GN/YL
EARTH POINT
L
N
E
FIGURE 05: WIRING DIAGRAM
4
3
2
1
BK