18
FIgurE 5: Operating/Configuration Screens
Cl
2
T=100F P= 85 psi
Superheat = 32 F
Control Water Temp
180 F
Heater Power
9.0 kW (50%)
Solenoid = Closed
Hold “+” to Open
Alarm Status
Normal
Enter Password
100
Temperature Units =F
Pressure Units = psi
Water Temp Alarm
Low= 160F High= 205F
Gas Pressure Alarm
250 psi
Super Heat Alm Temp
20F (0 = off)
Super Heat Alm Type
Non-latching
Select PRV on Duty
PRV#1/Relay1
Modbus Baud=250000
Node=1 Data=8/N/1
Cl
2
Pressure Span
300 psi
T180 S=180 O=50 E00
G=3.0 I=1.0 LT=5
Heater Sheath Temp
300 F
Select Gas Type
Cl
2
1
2
14*
13
12
11
10
9
8
7
6
5
4
3
17*
16*
15*
* These menus are referred to as hidden
screens and are not visible under normal
operation. To access these screens, go
to screen 13 and with the node number
blinking press and hold the down key
until screen 14 appears. The remaining
screens may be accessed by pressing
the down key after screen 14 appears.
Figure 5. Operating/Configuration Screens