Remark
V
:
When enter Parameter setting status, press “up” or “down” to choose parameter code; after choose one, press “Timer”
button to show this code’s setting value, and press “up” or “down” can set the value; After finish setting, press “Timer”
button to confirm and return to Parameter code status.
Electronic
expansion
valve(EEV)
F70
EEV opening query
0
–480
--
F71
EEV control mode
0
–2
0
F72
Manually set EEV opening
100
–480
350
F73
Set EEV superheat degree
-15
–15
5
F74
Set EEV discharge temp
85
–110
92
F79
Return gas temp.
--
System
Setting
F80
Password
OFF
0001 -- 9999
4321
-
“OFF” means no
password.
Set
“0000” to
clear password.
F85
Display sterilization total time
-
-
hour
Testing
F98
Force defrosting (refrigeration)
Control panel
display
“AdF”
Start compressor, 4-way
valve and fan motor. Press
any key to exit or 20 minutes
it will exit automatic.