HYDRO FLAME FA-79 AND HF-80 SERIES 

 

INSTALLATION AND OPERATING INSTRUCTIONS 

 
Sealed combustion system (Direct vent) Appliances for installation in Recreational Vehicles (Not tested for use with air 
filters or air conditioning) 
 

Model   

 

input 

Bonnet   

Type 

 

Electrical 

 

No. 

 

 

BTU/hr. Capacity  

Gas 

 

Rating 

 

FA-7920S (D or P) 

19.500  15,600   

Propane  

12V.D.C. 29 AMP 

 

FA-7920F (D or P) 

19.500  13,650   

Propane  

12V,D.C. 2.9 AMP 

 

FA-7916S (D or P) 

16,000  12,800   

Propane  

12V.D.C. 2.7 AMP 

 

FA-7916F (D or P) 

16,000  11,200   

Propane  

12V.D.C. 2.7 AMP 

 

FA-7912S (D or P) 

12,000  9,600 

 

Propane  

12V.D.C. 2.7 AMP 

 

FA-7912F (D or F) 

12,000  8.400 

 

Propane  

12V.D.C. 2.7 AMP 

 

HF.8012   (D or F) 

12,000  8,400 

 

Propane  

12V.D.C. 1.6 AMP 

 

Letters after the Model Number stand for: 

 

S = Side Ducted   F = Front Discharge  

D = Direct Spark Ignition   P = Piezo Ignition 

 
Overall Dimensions 

Minimum Clearances to Combustibles 

Length: 20 5/8"   

Top & Sides  

 

1/4" 

Height: 11 1/2"   

Air tube   

 

   0" 

Width:  9 5/8" 

 

Rear  

 

 

   0" 

Shipping wt.:  18 lbs. 

Front  

As required for servicing 

 

INSTALLATION 

This Furnace must be installed in accordance with these instructions and all National or Local Codes and CSA 
standards Z240.4 and Z240.6.1 or Z240,6.2 
The Furnace must be installed with the combustion air box (B) and exhaust tube (C) through an outside wall. 
 
The Furnace should be as near to the center of the vehicle as possible. 
1.  Provide a 11 1/4" High x 8 3/8" Wide Cabinet opening and 2 7/16" High x 4 15/16" Wide outside wall opening as 

shown in Fig. 3. 

2.  On side discharge (ducted models), remove left side knock-out plate and install two duct adapters. 
3.  Slide Furnace into cabinet opening. On side ducted Models Slide 4" D1A. Ducts over the adapters and seal with 

duct tape. 

4.  Gas Piping: Connect Gas supply line with a capacity to provide 11" W.C. Pressure to the gas control inlet fitting 

(3/4" minimum 0.0. tubing must be used) do not twist gas valve during piping. 

5.  Be sure that the Entire gas system is tight, properly supported and free of leaks. Do not fire any appliance until the 

entire system is fully checked out. Use a soap and water solution to detect gas leaks, never a lighted match or 
flame. 

NOTE

:  If local codes require an external gas "Shut off Valve", it must be located outside the furnace casing. 

6.  Electrical Wiring: With the Junction box cover removed route battery or 12V.D.C. and termostat leads through 

opening on the right side of furnace casing and connect to furnace wiring. 

 
CONNECTIONS 
Supply Leads 

 

 

 

Furnace Wiring 

12V.D,C. (+ & One Thermostat 

TO 

Thermo & 12V.D.C. + 

12V.D.C. (-) 

 

 

TO 

12V. D.C. - 

One Thermostat    

 

TO 

Thermostat 

 
Observe polarity of leads when connecting. 

NOTE

:  Supply leads other than thermostat should be 14 GA. Mm. 

www.ApacheOwners.com

Summary of Contents for FA-7920S D

Page 1: ...RPORATION FURNACE MAINTENANCE SERVICE MANUAL CAUTION READ PAGE 1 PRIOR TO FIRING YOUR FURNACE HYORO FLAME CORPORATION 1874 South Pioneer Road SALT LAKE CITY UTAH 84104 Phone 801 972 4621 RV 1 1 7 www ApacheOwners com ...

Page 2: ...ly filled with water and it is seldom that all of this water is removed The following often happens when the furnace is in operation The gas in a propane cylinder is liquid as it is drawn off it becomes a vapor as does a small amount of the water Then the gas vapor and water vapor proceed to the small orifice in the pressure regulator at 100 lbs PSI pressure or more Passing through this orifice th...

Page 3: ...should be closed tightly after pilot is lit and before main burner is turned on PILOT OUTAGE If the pilot flame will not stay lit when you release pilot knob check ignition flame size The flame should envelop the top 3 8 to 1 2 of thermocouple and should be approximately 1 1 2 long If pilot flame does not envelop the top 3 8 to 1 2 of the thermocouple with 1 1 2 total length turn pilot gas adjustm...

Page 4: ...C through an outside wall The Furnace should be as near to the center of the vehicle as possible 1 Provide a 11 1 4 High x 8 3 8 Wide Cabinet opening and 2 7 16 High x 4 15 16 Wide outside wall opening as shown in Fig 3 2 On side discharge ducted models remove left side knock out plate and install two duct adapters 3 Slide Furnace into cabinet opening On side ducted Models Slide 4 D1A Ducts over t...

Page 5: ...TIONS FA 79 D Models have direct spark ignition systems conforming to A N S Z2120 standards There is no pilot light To place furnace in operation 1 Turn gas valve to on position NOTE Some models may be equipped with a gas valve that does not have a gas control knob 2 Set thermostat to Lowest temperature setting then to desired temperature if thermostat has an off switch turn to on NOTE On initial ...

Page 6: ... 6 Do not operate the furnace through a battery charger 7 Do not attempt field repairs on the electrical module on D models 8 Do not install the furnace on top of carpeting or store flammable liquids or vapors in the vicinity 9 Do not install furnace where clearances from combustible materials can not be maintained 10 Do not attempt to ignite a direct ignition furnace with a match torch or flint t...

Page 7: ...6 www ApacheOwners com ...

Reviews: