9. MONITORING
Check the specified temperatures of the fluid after commissioning.
If these values are not stable and the system reaches excessive
temperatures, please check the following:
z
Fan direction of rotation (fan rpm if possible)
z
Electrical connections
z
Thermostats and pressure bypass valves
z
Cooling air flow and direction (if possible)
z
Fluid flow rate
z
I/O temperatures of fluid and air
z
Cleanliness of the cooling element surfaces
z
Maximum pressure of the system
10. FLUID COMPATIBILITY
OIL
Mineral: HL / HLP / HLVP according to DIN 51524
Synthetic: MIL-H, SKYDROL, EHC according to CETOP RP 77H
High viscosity: HFD
Ecological: HETG / HEPG / HEE according to CETOP RP 77H
Phosphate ester: HFD-R, HFD-U according to CETOP RP 77H
WATER
Oil-water: HFA according to CETOP RP 77H
Water-oil: HFB according to CETOP RP 77H
Water / glycol: HFC according to CETOP RP 77H
ATTENTION
For all other fluids please contact our Technical Department.
For coolers equipped with pump and pump & filter respectively
ACA, ACAF, OKA, OKAF, SCA, SCAF, OSCA, OSCAF, please contact
the Technical Department before using the above-mentioned fluids.
ATTENTION
For all mixture percentages HFA, HFB, HFC
please contact our Technical Department.