12
ETS 4100S IO-Link
Edition: 2020-07-20
HYDAC ELECTRONIC GMBH
Part No.: 670032
E
- Two-Point mode:
In the two-point mode the parameters SP1 and SP2 are used.
If the measured value reaches or exceeds the switching point SP1, the
SSC will switch to ON.
If the measured value falls below the switch back point SP2, the SSC will
switch to OFF.
SSC → ON,
if measured value ≥ SP1
SSC → OFF,
if measured value < SP2
o
Hyst (Subindex 3):
Hysteresis in °C with 1 decimal place.
The Hysteresis is used in the modes "Single-Point" and "Window"
(see above).
Q1 Configuration (Index 128):
Configuration of the switching output at PIN4 (C/Q1), % FS range for temperature
corresponds with the measured range, i.e. -25..+100 °C.
For operation in SIO mode only
o
Output function (Subindex 1):
Output function uses SP and RP at HNO and HNC (Hysteresis) or FL and FH
at FNO and FNC (window with fixed hysteresis 0.4 %FS, below FL and above
FH)
Default: Hysteresis function normally open (HNO) (selectable are Hysteresis
function normally open (HNO), Hysteresis function normally closed (HNC),
window function normally open (FNO
)
, window function normally closed (FNC))
o
Transistor function (P-n) (Subindex 2):
Transistor function at the output pin (NPN cannot be used at the IO-Link
master ports)
Default: PNP (wählbar sind PNP, NPN oder Push-Pull)
o
Upper setting value (SP/FH) (Subindex 3):
Upper setting value in % FS with 2 decimal places, i.e. 3175 = 31.75 %.
Setting value corresponds with SP at HNO and HNC (Hysteresis) or FH at
FNO and FNC (F = Fenster = window).
o
Lower setting value (RP/FH) (Subindex 4):
Lower setting value in % FS with 2 decimal places, i.e. 2550 = 25.50 %.
Setting value corresponds with RP at HNO and HNC (Hysteresis) or FL at
FNO and FNC (F = Fenster = window).