ETS 4100 HART
9
Status: 2016-12-20
HYDAC ELECTRONIC GMBH
Part no.: 669973
E
8.2 ETS 4100 HART with Pressure measurement as an option
Additional technical data with pressure option:
Input data
Measurement ranges
bar
16
40
60
100
250
400
600
Overload pressures
bar
32
80
120
200
500
800
1000
Burst pressure
bar
200
200
300
500
1000
2000
2000
Mechanical connection
G 1/2 A ISO 1179-2 with probe
Tightening torque,
recommended
45 Nm
Probe length
7 mm
Output data
Output signal Temperature
4 .. 20 mA with HART Protocol
Output signal Pressure
available via HART protocol as a digital signal
Accuracy to DIN 16086,
Max. setting
≤
± 0.25 % FS typ.
≤
± 0.5 % FS max.
Accuracy at minimum setting
(B.F.S.L)
≤
± 0.15 % FS typ.
≤
± 0.25 % FS max.
Temperature compensation
≤
± 0.008 % FS / °C typ.
≤
± 0.015 % FS / °C max.
Offset
Temperature compensation
≤
± 0.008 % FS / °C typ.
≤
± 0.015 % FS / °C max.
Span
Non-linearity at max. setting
according to DIN 16086
≤
± 0.3 % FS max.
hysteresis
≤
± 0.1 % FS max.
Repeatability
≤
± 0.05 % FS
Long-term drift
≤
± 0.1 % FS typ./ year
Ambient conditions
Compensated temperature
range
-25 .. +85 °C
Measuring Range Limits:
By means of HART Common Practice Commands, you have the opportunity to adjust the following measuring
ranges:
Additional measuring range limits of the secondary variable, pressure:
Lower measuring range limit
Upper measuring range limit
Measuring span
min
max
min
max
min
max
0 % FS
112.5 % FS
37.5 % FS
150 % FS
37.5 % FS
150 % FS